8
Contact:
®
NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD  21117
T: 410.753.8300
Toll Free: 800.253.3842
www.novatechweb.com
.  8 discrete inputs for dry contact switches
.  24 V dc provided on input high side 
.  Returns commoned internally
.  Pulse counting option
.  24 V dc bussed field power required
Module Specifications 
Inputs
Number of channels ...........................................................................8
OFF current ..........................................................................< 0.69 mA
ON current............................................................................> 2.24 mA
Wetting current .................................................................5 mA (typ.)
Minimum pulse width detected ...............................................3 ms
Maximum switching frequency (no-filtering)....................200 Hz
Isolation (any channel to Railbus) .....................................250 V ac
Configurable Parameters
Selectable input filter ...........................fast, slow or user defined
     (User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs................................................................enable /disable
Latch polarity......................................latch on high / latch on low
Pulse counting ..........................................................enable /disable
Response Time
I/O response time
Field event to new data available on Railbus............3 ms (max.)
 
Safety
FM non-incendive field wiring parameters (each channel)
...................V
oc
 = 30 V; I
sc
 = 15.2 mA; C
a
 = 0.12 μF; L
a
 = 151 mH
Power Supplies
Railbus (12V) current......................................................35 mA (typ.)
...........................................................................................55 mA (max.)
Bussed Field Power ......................................40 mA, @ 18—36 V dc
NT
-8110-DI-DC
Image Description
8-channel Discrete Input
24 V dc, non-isolated, module powered
Mechanical
Module Key Code..............................................................................B1
Module width ............................................................................42 mm
Weight............................................................................................170 g
Field Terminals 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8602-FT-ST 
Standard †
NT-8604-FT-FU
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8601-FT-NI
Non-incendive †
NT-8603-FT-FU
Non-incendive, 
fused
† External fusing of the field power supply is recommended 
in order to protect the field wiring.
NovaTech 8000 Series I/O Family
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks 
are properties of their respective owners. NovaTech is a registered 
trademark  of  NovaTech,  LLC.  The  information  in  this  literature  is 
subject to change without notice and is not to be construed as a 
warranty.  DS_8110_0607