Справочник Пользователя для Mitsubishi Electronics Mitsubishi Digital Electronics Automobile Accessories Frequency Inverter

Скачать
Страница из 52
9
MITSUBISHI ELECTRIC
FR-F 740 EC/E1
SYSTEM DESCRIPTION
International standards
The inverters of the FR-F 740 EC series are
designed so that they can be used world-
wide without any additional modifications
or certifications.
The units conform to the international
CE, UL, cUL, Gost and CCC standards.
User-selectable positive or negative
switching logic. Users can select posi-
tive or negative switching logic for in-
put and output signals, enabling
flexible and simple adaptation of the
units for varying world market
requirements.
Extended input power voltage range:
3~ 380-480 V (up to 500 V for 01800 and
above), 50/60 Hz
Tolerance:
−15%; +10%
Multilingual programming/control unit
(optional)
Support for a variety of international in-
dustrial bus systems
Internationally standardised, frequency
inverter configuration software package
for MS Windows, with multilingual user
interface
These features make the FR-F 740 EC a truly
international product that meets all relevant
standards and can be easily adjusted for na-
tional requirements.
R
R
C
DIN ISO 9001 /
EN 29001
Zertifikat: 09 100 4371
SELV
Electromagnetic compatibility
New technologies have been used to signi-
ficantly reduce the interference levels ge-
nerated by this frequency inverter.
The FR-F 740 EC conforms to the strict elec-
tromagnetic compatibility regulations of
the European Union (EMC Directive, Envi-
ronment 2). In order to meet these stan-
dards the FR-F700 inverters are fitted with
a new, integrated interference suppression
filter, which can easily be deactivated with
a jumper if necessary.
You can also further limit the make current
and reduce network interference by fitting
the input of the inverter with an optional
AC reactor and a DC reactor, which is con-
nected to special terminals on the inverter
unit.
The DC reactor is included as standard
equipment with models 00180 and above
and must be used with them.
Circuit boards with two coats of pro-
tective varnish
The frequency inverters with the E1 desig-
nation (standard, type 02160 and above)
have circuit boards with two coats of pro-
tective varnish.
This feature is available as an option for the
models up to type 01800. The twin coating
on the internal PCBs provides even better
protection against environmental influen-
ces. This is particularly important in appli-
cations sewage plants where the switchge-
ar cabinets are exposed to aggressive
fermentation gases that can reduce the
service life of the equipment.
Environment-Friendly and Internationally Compatible