  DISCONNECT ELECTRICAL POWER 
             to the boiler and heating system before 
servicing. Positively assure that no voltage is 
present. Lock electrical boxes to prevent someone 
from inadvertently restoring power before the 
heating system is safe to operate.
  NEVER DEFEAT OR JUMP OUT safety 
             devices.
  PROTECT EACH BOILER circuit with a 
             properly sized over-current protection 
device.
  MAKE ELECTRICAL CONNECTIONS 
             CAREFULLY according to the boiler’s 
wiring diagram and instructions
Refer to the Internal Wiring diagrams later in this 
manual.
1. 
Locate the wiring box on the left side of the 
boiler and open the cover (Figure 7-a).
2.
  Install a 120V disconnect near the boiler.
3.
  Connect the 120V wiring from the disconnect 
to the boiler's white (neutral), black (hot), 
and green (ground) labeled "120VAC Power 
supply".  Do not reverse polarity.
4.
  Connect the 120V wiring from the circulator 
to the white (neutral) yellow (hot) wires 
marked "circulator".
  WIRE AN ADDITIONAL SAFETY LIMIT 
             such as a low water cutoff or temperature 
limit device, other than an IQ
™ Control device, 
in series with the 120V circuit used to power the 
boiler. Do not alter the boiler’s factory wiring when 
adding an additional limit.
.  CONNECT ELECTRICAL WIRING
5.
  Connect the 24V wiring from the thermostat 
to the "T-T" terminals on the Option Control 
Panel.
6.
  To connect other external devices, refer to 
the instructions included with these devices.
7-a
1

1
2
3
T
T
7-b