APPeNDIX B – VeNtING
  VENT THIS BOILER according to the instructions. Failure to do so may cause products of 
           combustion to enter the building resulting in severe property damage, personal injury or death.
i        
  Install this boiler according to this manual and the National Fuel Gas Code, ANSI Z223.1/NFPA 54,  
     the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the     
           local building codes. Contact local building or fire officials about restrictions and installation 
inspection in your area.
If you are removing an existing boiler from a gas 
vent or chimney that is also used to vent other gas 
appliances:
1.
  Seal any unused openings in the  
common venting system.
2.
  Visually inspect the venting system    
for proper size and horizontal pitch    
and determine there is no blockage or  
restriction, leakage, corrosion, and other  
deficiencies which could cause an    
unsafe condition.
3.
  Resize the common venting system    
to approach the minimum size as  
 
determined using the National Fuel Gas  
Code, ANSI Z223.1 and/or CAN/CSA  
B149.1, Installation Codes.
4.
  Check the draft of each remaining  
 
appliance using the procedure described  
in Appendix G, checking draft and  
combustion.
5.
  Correct any draft problems before  
 
placing the gas appliances back into  
service.
i        
 
In addition to previously mentioned vent 
           codes of the main general guidelines, 
           atmospheric vented installations must 
also be in accordance with the Standard for 
Chimneys, Fireplaces, Vents and Solid Fuel 
Burning Appliances, ANSI/NFPA 211.  For Canada 
installations, refer to the Natural Gas and LP 
Installation Code, CAN/CSA- B149.1.