Справочник Пользователя для Force10 Networks Force10 TeraScale E-Series E1200i

Скачать
Страница из 105
Installing and Maintaining the E1200i System
51
Figure 21   24 Port 1GE and 2-Port 10GE Line Card Port Numbering 
Blank Panels 
Blank panels for RPMs, SFMs, and line cards must be installed in empty slots to control airflow. If a slot is 
not filled for more than five minutes, the following message appears on the console:
%CHMGR-2-MINORTEMP: Minor alarm: chassis temperature high (SFM 
temperature reaches or exceeds threshold of 65C)
Blank panels are shipped with the system to ensure that all chassis slots are installed with operational 
modules or blanks.
Preparing and Installing RPMs and Line Cards
To prolong the life of the EMI seals, begin installing cards in the right-most slot (slot 13), filling the slots 
leftward (slot 12, then slot 11, then slot 10, and so on). 
Caution: To avoid a chassis over-temperature condition, install blanks for RPMs, SFMs, and line card slots 
not in use. Always replace cards or blanks immediately.
Port 0
Port 1
Port 2
Port 3
Port 4
24-port 1GE line card
2-port 10GE line card
FN00020A
PORT 0