1 Outline
1.3 Cautions on Creation of Fundamental Programs
18
FXCPU Structured Programming Manual
(Application Functions)
1.3.3
Circuits not available in structured ladder programs and countermeasures
1. Bridge circuit
A circuit in which the current flows in both directions should be changed as shown in the right figure (so that a
circuit without D and a circuit without B are connected in parallel).
2. Coil connection position
• You can program a contact on the right side of a coil. In this case, make sure to program a coil (including a 
function or function block) at the end of the circuit.
1.3.4
Handling of general flags
The following flags are valid in general sequence instructions:
(Examples)
M8020:Zero flag
M8021:Borrow flag
M8022:Carry flag
M8029:Instruction execution complete flag
M8090:Block comparison signal
*1
M8328:Instruction non-execution flag
*1
M8329:Instruction execution abnormal complete flag
*2
M8304:Zero flag
*1
M8306:Carry flag
*1
*1.
Supported only in FX
3U
/FX
3UC
 PLCs.
*2.
Supported only in FX
3U
/FX
3UC
/FX
3G
 PLCs.
Each of these flags turns ON or OFF every time the PLC executes a corresponding instruction. These flags
do not turn ON or OFF when the PLC does not execute a corresponding instruction or when an error occurs.
Because these flags are related to many sequence instructions, their ON/OFF status changes every time the
PLC executes each corresponding instruction.
Refer to examples in the next page, and program a flag contact just under the target sequence instruction.
A
B
C
E
D
C
E
A
B
A
E
C
D
F
F
Or
A
B
D
A
B
D
C
E
C
E
A
B
E
D
C