Инструкции По Установке для Maytag MLE24PDAWW

Скачать
Страница из 44
8
Venting Requirements
WARNING: TO REDUCE THE RISK OF FIRE, THIS DRYER 
MUST BE EXHAUSTED OUTDOORS.
n
   Following these venting requirements will minimise ducting  
air noise.
n
   Gas dryers should only be installed in a room if the room  
meets the appropriate ventilation requirements specified  
in the national installation regulations. Make sure the room 
containing the dryer has an adequate air supply for gas 
combustion and drying operation. A window or equivalent 
means of ventilation must be opened in the room when the 
dryer is in use (an equivalent form of opening includes an 
adjustable louver, hinged panel, or other means of ventilation 
that opens directly to outside air). Adequate ventilation has  
to be provided to avoid the backflow of gases into the room 
from other fuel-burning appliances, including open fires  
(i.e. available airflow into the room should match airflow  
out from the room).
n
   The design of the flue system should be such that any 
condensate formed when operating the dryer from cold  
shall either be retained and subsequently re-evaporated or 
discharged. Following these instructions should adequately 
meet this requirement.
n
   Dryer exhaust must not be connected into any gas vent, 
chimney, wall, ceiling, attic, crawlspace, or a concealed space 
of a building. Only rigid or flexible metal vent shall be used for 
exhausting.
n
   Do not use an exhaust hood with a magnetic latch.
n
   Do not install flexible metal vent in enclosed walls, ceilings,  
or floors.
n
   Only a 4" (102 mm) heavy metal exhaust vent and clamps 
may be used.
n
   Use clamps to seal all joints. Vent must not be connected  
or secured with screws or other fastening devices which 
extend into the interior of the vent and catch lint. Do not  
use duct tape.
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in death
or fire.
Flexible metal appliance connector
n
   It is recommended that a new flexible stainless steel gas line, 
design-certified by CSA International, be used for connecting 
the dryer to the gas supply line. (The gas pipe which extends 
through the lower rear of the dryer is provided with 3/8" male 
pipe thread.) 
n
   Do not kink or damage the flexible stainless steel gas line 
when moving the dryer.
Rigid pipe connection
The rigid pipe connection requires a combination of pipe fittings 
to obtain an in-line connection to the dryer. 
n
   Must include a shut-off valve:
 
 The supply line must be equipped with a manual shut-off 
valve. In the U.S., the valve 
must be installed within  
6 ft. (1.8 m) of dryer in 
accordance with National 
Fuel Gas Code, ANSI 
Z223.1. In Canada, an 
individual manual shut-off 
valve must be installed in 
accordance with the B149 
installation codes CAN/
CGA B149.1 and CAN/
CGA B149.2. This valve 
should be located in the 
same room as the dryer. It 
should be in a location that 
allows ease of opening and closing. Do not block access to 
shut-off valve. The valve is for turning on or shutting off gas to 
the dryer.
n
   Installed in a confined area:
 
 If the dryer is installed in a confined area such as a bathroom, 
provision must be made for enough air for combustion and 
ventilation. Check governing codes and ordinances or refer to 
the “Recessed Area Installation Instructions” in the “Location 
Requirements” section.
Gas Supply Pressure Testing
A 1/8" NPT minimum plugged tapping, accessible for gauge 
testing, must be installed immediately upstream of the installed 
shut-off valve to the dryer. 
The dryer must be disconnected from the gas supply piping 
system during any pressure testing of the system at test 
pressures in excess of 1/2 psig.
A. Gas supply line
B. Shutoff valve “open” position
C. To range
A
B
C
Gas Supply Line
Recommended method
n
   Provide a gas supply line of 1/2" rigid (IPS) pipe to the dryer 
location. Pipe joint compounds that resist the action of LP  
gas must be used. Do not use TEFLON
®†
 tape. With LP gas, 
piping or tubing size can be 1/2" minimum. Usually, LP gas 
suppliers determine the size and materials used in the system.
 Alternate  method
n
   The gas supply may also be connected using 3/8" approved 
copper or aluminum tubing. If the total length of the supply 
line is more than 20 feet (6.1 m), larger tubing will be required. 
If using natural gas, do not use copper tubing. Pipe joint 
compounds that resist the action of LP gas must be used.
†® TEFLON is a registered trademark of E.I. Du Pont De Nemours and 
Company.
D
B
C
A
A. Gas supply line
B. Shutoff valve in “open” position
C. To dryer
D. NPT 1/8" min. plugged tapping
Improper venting can cause moisture and lint to collect 
indoors, which may result in:
Moisture damage to woodwork, furniture, paint, wallpaper, 
carpets, etc.
Housecleaning problems and health problems.
4"
(102 mm)
Heavy metal 
exhaust vent