METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8” (11-1/8” WITH SUB-BASE)
FIELD FABRICATED
Zoneline units can be installed in walls of greater
depth than the wall case. Where the case recession
is less than 3” and where it is possible to waterproof
the exposed sides and top of the opening, the
suggested procedure is to apply a flashing to the
bottom of the wall case as shown on page 29. Where
waterproofing is questionable or not possible, or for
installations in walls of greater depth, the following
is a suggested application procedure. It involves the
field
 fabrication
 of a case extension. Since the wall
case is a water bearing container, the extension
likewise must also be water bearing and the
connection between the two must be watertight. The
case extension must contain splitters to prevent
recirculation of the outdoor air circuit.
1. The case extension is field fabricated. The
entension depth “D” should allow for a minimum
outdoor projection of 1/4”. This allows for room
cabinet clearance to the finished wall and ample
surfaces to apply sealant or caulking for a tight
weather seal between the completed wall case/
extension assembly and the wall opening. It is
recommended that the extension be painted and
corner and lap joints be additionally sealed with a
quality grade sealant.
2.  The wall case and extension should be connected
prior to installation in the wall opening. A quality
grade sealant should be applied to all four (4)
butting flanges. Use bolts and nuts or oversized
self tapping screws (driven from the wall case to
the extension) to attach the two assemblies. Clean
all drain holes of excess sealant. The assembly
must be free draining.
3. Install flashing, using a quality grade sealant
between the flashing and wall as shown in section
A-A below.
4.  Install the wall case/extension assembly following
procedures described for a standard installation.
See diagrams below. The assembly should be
sealed or caulked to the wall around all four sides
both outdoors and indoors.
     NOTE: The wall case/extension assembly should
be level in all directions.
5. Suggested materials for case extension and
flashing should be non-ferrous metals. Minimal
acceptable material: Galvanized G-90 painted.
SEALANT - ALL
FOUR (4) FLANGES
6-1/4” +
 1/4”
D
AS REQ’D.
SPLITTER BETWEEN
AIR INTAKE AND
DISCHARGE
2” MIN.
13 3/4”  + D”
FLASHING (FIELD SUPPLIED)
EXTENSION
(FIELD
SUPPLIED)
10-5/8” 
+
 1/4”
RAB71/77
WALL CASE
CUT DRAIN SLOTS
IN BOTH FLANGES
(FOUR REQUIRED)
TO MATCH DRAIN
HOLES IN RAB71/77
FLANGES AND
DRAIN HOLE
LOCATIONS
SAME AS ON
WALL CASE
1” WIDE
45° DRIP LIP
ALL 4
SIDES
SECTION A-A
BASEPAN/FLANGE DESIGN
SHOWING SEALANT LOCATIONS.
ALL 4 FLANGES
EXTENSION
ALL 4 SIDES
WALL CASE
FLASHING
WALL
ROOM
CABINET
WALL -
ANY
CONSTRUCTION
1/4” MIN.
CASE
EXT.
RAB71/77
CAULK*
SEE DETAIL
SECTION A-A
*Caulk around perimeter of wall case all four sides
where it joins the building.
CAULK*
1-1/2”
(4 SIDES)