Инструкции По Установке для Miele DA6690W
Installation
35
c
Air vent positioned at top for recirculation
de
Mounting area (only d is required for recirculation ventilation hoods). Wall
and ceiling area for exhaust duct opening and for wall socket installation.
Only the wall socket installation is required for recirculation hoods.
Vent collar 6" (150 mm), with adapter 5" (125 mm).
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop,
follow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Minimum distance S
Cooking appliance
Miele
appliance
Non-Miele
appliance
Electric/Induction cooktop
24" (610 mm)
Electric grill, deep fat fryer (electric)
26" (660 mm)
Multi-burner gas cooktop
≤ 43,000 BTU/hr (12.6 W),
no burner > 15,000 BTU/hr (4.5 kW).
26" (660 mm)
30" (760 mm)
Multi-burner gas cooktop
≤ 73,800 BTU/hr (21.6 W),
no burner > 16,500 BTU/hr (4.8 kW)
30" (760 mm)
Multi-burner gas cooktop
> 73,800 BTU/hr (21.6 W),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Not possible
Single-burner gas cooktop
≤ 20,500 BTU/hr (6 kW)
26" (660 mm)
30" (760 mm)
Single-burner gas cooktop
≤ 27,600 BTU/hr (8.1 kW)
30" (760 mm)
Single-burner gas cooktop
> 27,600 BTU/hr (8.1 kW)
Not possible