INVERTER SETTING
17
3.4  Operation and Speed Command Write
In the CC-Link operation mode, commands from the external terminals and sequence program are as listed below:
(For Pr. 180 to Pr. 183 (input terminal function selection), different inverters have different functions. For full information, refer
to the inverter manual.)
Pr. 338 "operation command write"
0: PLC
0: PLC
1: External
1: External
Control
location
selection
Pr. 339 "speed command write"
0: PLC
1: External
0: PLC
1: External
Remarks
Forward rotation command (STF)
PLC
PLC
External
External
Reverse rotation command (STR)
PLC
PLC
External
External
Reset (RES)
Both
Both
Both
Both
CC-Link operation frequency
PLC
PLC
 2
External
External
Fixed functions
(Functions
equivalent to
terminals)
 4
External
External
0
Low-speed operation command (RL)
PLC
External
PLC
External
Pr. 59 = 0
1
Middle-speed operation command (RM)
PLC
External
PLC
External
Pr. 59 = 0
2
High-speed operation command (RH)
PLC
External
PLC
External
Pr. 59 = 0
3
Second function selection (RT)
PLC
PLC
External
External
4
Current input selection (AU)
Both
Both
5
Start self-holding selection (STOP)
External
External
6
Output shut-off (MRS)
Both
Both
External
External
(Note)
7
External thermal relay input (OH)
External
External
External
External
8
15-speed selection (REX)
PLC
External
PLC
External
Pr. 59 = 0
16
PU operation-external operation
switching (X16)
External
External
External
External
Select
iv
e f
unct
ions
Pr.
 180 t
o
 Pr.
 183 set
ti
ngs
18 Magnetic flux-V/F switching (X18)
PLC
PLC
External
External
RH, RM, RL
selection
functions
Remote setting (RH, RM, RL)
PLC
External
PLC
External
Pr. 59 = 1, 2