INVERTER SETTING
17
3.4 Operation and Speed Command Write
In the CC-Link operation mode, commands from the external terminals and sequence program are as listed below:
(For Pr. 180 to Pr. 183 (input terminal function selection), different inverters have different functions. For full information, refer
to the inverter manual.)
(For Pr. 180 to Pr. 183 (input terminal function selection), different inverters have different functions. For full information, refer
to the inverter manual.)
Pr. 338 "operation command write"
0: PLC
0: PLC
1: External
1: External
Control
location
selection
location
selection
Pr. 339 "speed command write"
0: PLC
1: External
0: PLC
1: External
Remarks
Forward rotation command (STF)
PLC
PLC
External
External
Reverse rotation command (STR)
PLC
PLC
External
External
Reset (RES)
Both
Both
Both
Both
CC-Link operation frequency
PLC
PLC
2
External
External
Fixed functions
(Functions
equivalent to
terminals)
(Functions
equivalent to
terminals)
4
External
External
0
Low-speed operation command (RL)
PLC
External
PLC
External
Pr. 59 = 0
1
Middle-speed operation command (RM)
PLC
External
PLC
External
Pr. 59 = 0
2
High-speed operation command (RH)
PLC
External
PLC
External
Pr. 59 = 0
3
Second function selection (RT)
PLC
PLC
External
External
4
Current input selection (AU)
Both
Both
5
Start self-holding selection (STOP)
External
External
6
Output shut-off (MRS)
Both
Both
External
External
(Note)
7
External thermal relay input (OH)
External
External
External
External
8
15-speed selection (REX)
PLC
External
PLC
External
Pr. 59 = 0
16
PU operation-external operation
switching (X16)
switching (X16)
External
External
External
External
Select
iv
e f
unct
ions
Pr.
180 t
o
Pr.
183 set
ti
ngs
18 Magnetic flux-V/F switching (X18)
PLC
PLC
External
External
RH, RM, RL
selection
functions
selection
functions
Remote setting (RH, RM, RL)
PLC
External
PLC
External
Pr. 59 = 1, 2