Справочник Пользователя для Mitsubishi Electronics 2033C

Скачать
Страница из 48
 
 
 
MITSUBISHI 
ELECTRIC
 
2033C SERIES UPS 
OWNERS / TECHNICAL MANUAL 
Page Number: 
1-2 
 
MITSUBISHI ELECTRIC 2033C SERIES UPS   
 
 
 
 
 
 
This UPS does not include an AC input circuit breaker (MCCB) to protect the 
bypass and main input circuit.    The AC input circuit breaker (MCCB) is to be field 
supplied and installed.    Circuit breaker (MCCB) specifications are as follows: 
 
Capacity 
(kVA) 
AC input 
Voltage (Vac) 
AC input 
Rating (Aac) 
Recommended 
Breaker (A) 
7.5 208  23  30 
10 208  30  35 
15 208  45  60 
20 208  61  75 
30 208  91  125 
40 208 121  150 
50 208 151  200 
 
AC output and DC input overcurrent protection and disconnection devices shall be field 
supplied and installed. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
WARNING  2