Справочник Пользователя для Honeywell XL 800 SERIES

Скачать
Страница из 36
Excel 800 
Description of the I/O Modules 
 21 
EN1B-0410GE51 
R0908A 
C-Bus Termination Switch S1 
The XCL8010AU
 
Controller Module features a 3-position C-
Bus termination switch S1. 
This switch must be set in accordance with the given C-Bus 
configuration. 
 
 
Fig. 34. C-Bus termination switch 
 
Table 21. XCL8010AU
 
C-Bus termination switch S1 
settings 
switch setting 
S1 
baud rate 
9.6k all 
Up to 9600 baud (default setting) 
76k mid 
Up to 76800 baud without bus termination  
76k end 
Up to 76800 baud with bus termination 
controller at the end of the C-Bus 
 
Memory 
Table 22. XCL8010AU memory 
memory 
size 
usage 
SRAM 512 
KB 
For controller application, 
modem trend and firmware 
RACL application: 128 KB 
Total application: 192 KB 
Flash 2 
MB 
Firmware (1 MB) and application 
(1 MB) storage 
EPROM 
128 KB  For bootstrap loader 
 
NOTE: The 
XCL8010AU
 
Controller Module does not 
contain a battery. RAM (data and realtime 
clocktime) is buffered for 3 days by a super 
capacitor. 
 
Description of the I/O Modules 
Common Features 
Switches Located on the Terminal Socket 
Table 23. Terminal socket switches 
feature 
function 
Service button 
S1 
•  LED test, see section "Troubleshooting" 
on page 31 
•  L
ON
W
ORKS
 service button functionality 
for L
ON
W
ORKS
 Bus I/O modules 
Hex switch S2 
•  Module addressing for Panel Bus 
I/O modules 
 
LEDs Located on the I/O Module 
Table 24. LEDs on I/O module 
feature 
function 
Service LED 
(yellow) 
•  Service information, see section 
"Troubleshooting" on page 31 
Power LED 
(green) 
•  Information on power supply, see section 
"Troubleshooting" on page 31  
 
For the location of these elements, see figures of the 