XL800 Series Power Consumption 
When selecting the appropriate power supply, the power 
consumption of the XL800 modules must be taken into 
account. 
Table 3. XL800 power consumption 
 
max. power consumption 
model 
24 Vac, 60 Hz 
24 Vdc 
XCL8010AU with 
watchdog load 
690 mA 
640 mA 
XCL8010AU without 
watchdog load 
190 mA 
140 mA 
XF821AU, XFL821AU 
130 mA 
80 mA 
XF822AU, XFR822AU, 
XFL822AU, XFLR822AU 
160 mA 
90 mA 
XF823AU, XFL823AU 
180 mA 
130 mA 
XF824AU, XFR824AU, 
XFL824AU, XFLR824AU 
140 mA 
90 mA 
XFR825AU 
140 mA 
90 mA 
 
I/O Modules 
Variants of I/O Modules 
There are two variants of I/O modules: 
•  Panel Bus I/O modules with communication via Panel Bus 
(light-gray housings) 
Modules are automatically commissioned (with firmware 
download) by the XCL8010AU 
•  L
ON
W
ORKS
 Bus I/O modules (dark-gray housings) with 
communication via L
ON
W
ORKS
 (FTT10-A, link power 
compatible) for easy integration and use with 3
rd
-party 
controllers 
 
Terminal Sockets 
I/O modules are mounted on the appropriate terminal 
sockets. Panel Bus I/O modules and L
ON
W
ORKS
 Bus I/O 
modules use the same terminal sockets. 
 
Color Coding 
To distinguish modules and components, the following color 
coding is used: 
Table 4. Color coding of Excel 800 Modules 
color 
part 
red 
All of the user-accessible adjustable 
mechanical parts (i.e., bridge connectors and 
locking mechanism) and operating controls 
(manual overrides, etc.) 
light-gray 
Panel Bus I/O modules 
dark-gray 
L
ON
W
ORKS
 Bus I/O modules