NATIONAL POWER DEVIATION STANDARDS 
AUSTRALIA / NEW ZEALAND 
COMPONENTS COMPLY WITH THE RELEVANT PORTIONS OF IEC 60950 OR THE 
APPLICABLE COMPONENT STANDARD OR THE RELEVANT AUSTRALIAN / NEW ZEALAND 
STANDARD. 
AC POWER DISTRIBUTION SYSTEMS CLASSIFIED AS TT OR IT ARE NOT ALLOWED 
INTENDED FOR USE ON A TN SYSTEM. 
-------------------------------------------------------------------- 
Rated  
Nominal 
Current of  
cross-sectional 
Equipment  
area 
(A)  
(mm²) 
-------------------------------------------------------------------- 
0.2  
<=  
3 0.5* 
3  
<=  
7.5 0.75 
7.5  
<=  
10 (0.75) 1.00 
10  
<=  
16 (1,0) 1.5 
16  
<=  
25 2.5 
25  
<=  
32 4 
32  
<=  
40 6 
40  
<=  
63 10 
63  
<=  
80 16 
80  
<=  
100 25 
100  
<=  
125 35 
125  
<=  
160 50 
160  
<=  
190 70 
190  
<=  
230 95 
 
DENMARK 
CERTAIN TYPES OF CLASS I APPLIANCES MAY BE PROVIDED WITH PLUG NOT 
ESTABLISHING EARTHING CONTINUITY WHEN INSERTED INTO DANISH SOCKET-OUTLETS. 
 
"VIGTIGT ! 
LEDEREN MED GRØN/GUL ISOLATION MÅ KUN 
TILSLUTTES EN KLEMME MÆRKET 
(IEC 417, NO. 5019) ELLER (IEC 417, NO. 5017) 
 
FOR TILSLUTNING AF DE ØVRIGE LEDERE, SE MEDFØLGENDE 
INSTALLATIONSVEJLEDNING 
 
SUPPLY CORD OF SINGLE-PHASE EQUIPMENT HAVING A RATED CURRENT NOT 
EXCEEDING 13 A SHALL BE PROVIDED WITH A PLUG ACCORDING TO THE HEAVY 
CURRENT REGULATIONS, SECTION 107-2-D1. CLASS I EQUIPMENT PROVIDED WITH 
SOCKET-OUTLETS WITH EARTH CONTACT OR WHICH ARE INTENDED TO BE USED IN 
LOCATIONS WHERE PROTECTION AGAINST INDIRECT CONTACT IS REQUIRED ACCORDING 
TO THE WIRING RULES SHALL BE PROVIDED WITH A PLUG IN ACCORDANCE WITH 
STANDARD SHEET DK 2-1A OR DK 2-5A. IF POLY-PHASE EQUIPMENT AND SINGLE-PHASE