SSC Series Central Chilling Stations 
4-8  High Pressure Cutout 
This electro-mechanical safety feature opens the control circuit if 
the system condensing pressure exceeds a safe level. 
 
High pressure cutout setting 
Model 
psi 
kPa 
bars 
SSC Series water-cooled chilling stations 
290 psi 
2,000 kPa 
20 bars 
SSC Series remote air-cooled chilling stations 
375 psi 
2,586 kPa 
26 bars 
 
 
Important! 
The high pressure cutout is a manual reset control, 
so you should reset it once
 
If the problem persists, call a refrigeration service technician  
to analyze the problem and to reset the control. 
 
 
4-9  Low Pressure Cutout 
This encapsulated switch safety feature prevents the compressor 
suction pressure from dropping below a pre-set point. It is factory 
set to open the control circuit when pressure drops below a safe 
level. The chiller will need to be restarted when the suction 
pressure reaches above 65 psi (448.2 kPa/4.5 bars). 
 
 
Opens control circuit @ 
Resets control circuit @ 
Model 
psi 
kPa 
bars 
psi 
kPa 
bars 
SSC Series water-cooled chilling stations 
15 psi  103.4 kPa  1.0 bars  30 psi  206.9 kPa  2.1 bars 
SSC Series remote air-cooled chilling 
stations 
15 psi  103.4 kPa  1.0 bars  30 psi  206.9 kPa  2.1 bars 
 
 
4-10  Flow Switch 
The flow switch shuts down the chiller if the evaporator water flow 
falls below a safe operating gallons-per-minute (liters-per-minute) 
flow rate.