Справочник Пользователя для Mitsubishi Electronics QD75P1

Скачать
Страница из 860
 
 
 
4 - 14 
MELSEC-Q
4      INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT 
 
4.3.2 Wiring of the differential driver common terminal   
When the differential driver output system (QD75D N/QD75D ) is used, a potential 
difference between commons may occur between the differential driver common 
terminal and the differential receiver common terminal of the drive unit. To remove the 
potential difference between commons, connect the differential driver common terminal 
of the QD75D N/QD75D   and the differential receiver common terminal of the drive 
unit. 
When the common terminal of the drive unit is photocoupler-connected, the wiring to 
the differential driver common terminal of the QD75D N/QD75D   is not needed 
since a potential difference between commons does not exist. 
(For the drive unit specifications, refer to the manual of the used drive unit.) 
 
 Applicable connectors 
To wire the differential driver common terminal, use the wire applied to the following 
table. 
Wire diameter 
Type 
Material 
Temperature rating 
0.24 to 2.5mm
2
   
(24 to 12AWG) 
Stranded wire/single wire
Copper 
75˚C or more 
 
 Wiring example 
The following shows an example of wiring to the differential driver common terminal of 
the QD75D N/QD75D . 
Up to two cables can be connected to one differential driver common terminal. (For 
details, refer to Section 3.1 "Performance specifications". 
 
To differential receiver common terminal of drive unit
Module front
Differential driver common terminal
Module bottom
 
Module front
Module bottom
Insert until hook
catches.
 
Module side