8 - 23 
MELSEC-Q
8   OPR CONTROL 
 
8.3 Fast OPR 
8.3.1 Outline of the fast OPR operation 
 Fast OPR operation 
 
After establishing OP position by a machine OPR, positioning control to the OP 
position is executed without using a near-point dog or a zero signal. 
The following shows the operation during a fast OPR start.   
 
1)  The fast OPR is started.   
2)  Positioning control to the OP position established by a machine OPR begins at 
the speed set in the OPR parameters ( Pr.43   to   Pr.57 ). 
3)  The fast OPR is completed.   
 
OPR speed
Machine OP
(OP position)
Axis operation 
status
Standby
Position control
Standby
Pr.46
M
OP
Positioning to the OP
Md.26
Fast OPR start
(Positioning start signal)
[Y10,Y11,Y12,Y13]
 
Fig. 8.16 Fast OPR