Справочник Пользователя для Mitsubishi Electronics QD75P1

Скачать
Страница из 860
 
 
 
9 - 103 
MELSEC-Q
9   MAJOR POSITIONING CONTROL 
 
9.2.18 Position-speed switching control 
In "position-speed switching control" ("   Da.2   Control system" = Forward run: 
position/speed, Reverse run: position/speed), before the position-speed switching 
signal is input, position control is carried out for the movement amount set in 
"   Da.6   Positioning address/movement amount" in the axis direction in which the 
positioning data has been set.    When the position-speed switching signal is input, the 
position control is carried out by continuously outputting the pulses for the speed set in 
"   Da.8   Command speed" until the input of a stop command. 
The two types of position-speed switching control are "Forward run: position/speed" in 
which the control starts in the forward run direction, and "Reverse run: position/speed" 
in which control starts in the reverse run direction. 
 
  Switching over from position control to speed control 
 
(1)  The control is switched over from position control to speed control by 
executing the external command signal set in "position-speed switching signal". 
(2)  Besides setting the positioning data, the "   Cd.26   Position-speed switching 
enable flag" must also be turned ON to switch over from position control to 
speed control. (If the "   Cd.26   Position-speed switching enable flag" turns 
ON after the position-speed switching signal turns ON, the control will continue 
as position control without switching over to speed control. The control will be 
switched over from position control to speed control when the position-speed 
switching signal turns from OFF to ON again. Only speed control will be 
carried out when the "   Cd.26   Position-speed switching enable flag" and 
position-speed switching signal are ON at the operation start.)   
 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
Axis 1  Axis 2  Axis 3
Axis 4
 Cd.26  
Position-
speed 
switching 
enable 
flag 
Set "1: Switch from position 
control to speed control when the 
external command signal [CHG] 
turns ON". 
1532 1632 1732
1832
 
  Position-speed switching signal setting 
 
The following table shows the items that must be set to use the external command 
signals (CHG) as position-speed switching signals. 
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address 
Axis 1  Axis 2  Axis 3
Axis 4
 Pr.42  
External 
command 
function 
selection 
Set the "2: speed-position and 
position-speed switching 
requests". 
62 212 362
512
 Cd.8 
 
External 
command 
valid 
Set "1: Validate external 
command". 
1505 1605 1705
1805
  Refer to Section 5.2 "List of parameters" and Section 5.7 "List of control data" for information on the 