6 - 37 
MELSEC-Q
6      SEQUENCE PROGRAM USED FOR POSITIONING CONTROL 
 
6.5.4 Continuous operation interrupt program 
During positioning control, the control can be interrupted during continuous positioning 
control and continuous path control (continuous operation interrupt function). When 
"continuous operation interruption" is execution, the control will stop when the 
operation of the positioning data being executed ends. To execute continuous 
operation interruption, set "1: Continuous operation interrupt request" for 
"   Cd.18   Continuous operation interrupt request". 
 
[1]   Operation during continuous operation interruption 
 
Start 
Positioning data No. 10
Positioning data No. 11
Positioning data No. 12
Stop command ON or 
continuous operation interrupt request
V
t
Stop process at continuous operation 
interrupt request
Stop process when stop command turns ON
 
 
Fig. 6.12 Operation during continuous operation interruption 
 
 
[2]   Restrictions 
 
(1)  When the "continuous operation interrupt request" is executed, the positioning 
will end. 
Thus, after stopping, the operation cannot be "restarted". 
When "   Cd.6   Restart command" is issued, a warning "Restart not possible" 
(warning code: 104) will occur. 
(2)  Even if the stop command is turned ON after executing the "continuous 
operation interrupt request", the "continuous operation interrupt request" 
cannot be canceled. 
Thus, if "restart" is executed after stopping by turning the stop command ON, 
the operation will stop when the positioning data No. where "continuous 
operation interrupt request" was executed is completed. 
 
Axis 2
Axis 1
Positioning for positioning data No. 12 
is not executed
Positioning with positioning data No. 10
Positioning with positioning data No. 11
Continuous operation 
interrupt request
Positioning ends with continuous
operation interrupt request