9   MAJOR POSITIONING CONTROL 
 
9.2.7 2-axis fixed-feed control (interpolation) 
In "2-axis fixed-feed control" ("   Da.2   Control system" = fixed-feed 2), two motors are 
used to carry out fixed-feed control in a linear path while carrying out interpolation for 
the axis directions set in each axis.   
In fixed-feed control, any remainder of the movement amount designated in the 
positioning data is rounded down if less than that required for control accuracy to 
output the same amount of pulses. 
(Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.) 
 
 Operation chart 
 
In incremental system 2-axis fixed-feed control, the addresses ( Md.20   Current 
feed value) of the current stop position (start addresses) of both axes are set to "0". 
Linear interpolation positioning is then carried out from that position to a position at 
the end of the movement amount set in "   Da.6   Positioning address/movement 
amount". The movement direction is determined by the sign of the movement 
amount.  
 
Designated movement
amount
Designated movement
amount
(0,0)
(0,0)
(0,0)
X axis
Y axis
" Md. 20  Current feed value" of each axis
is set to "0" at the positioning start
 
 
 Restrictions 
 
(1)  An axis error "Continuous path control not possible" (error code: 516) will 
occur and the operation cannot start if "continuous path control" is set in 
"   Da.1   Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.) 
(2)  If the movement amount of each axis exceeds "1073741824 (=2
30
)" when "0: 
Composite speed" is set in "   Pr.20   Interpolation speed designation method", 
the error "Outside linear movement amount range" (error code: 504) occurs at 
a positioning start and positioning cannot be started. (The maximum 
movement amount that can be set in "   Da.6   Positioning address/movement 
amount" is "1073741824 (= 2
30
)". 
(3)  "Fixed-feed" cannot be set in "   Da.2   Control system" in the positioning data 
when "continuous path control" has been set in "   Da.1   Operation pattern" of 
the immediately prior positioning data. (For example, if the operation pattern of 
positioning data No. 1 is "continuous path control", fixed-feed control cannot 
be set in positioning data No. 2.) An axis error "Continuous path control not 
possible" (error code: 516) will occur and the machine will carry out a 
deceleration stop if this type of setting is carried out.