11   MANUAL CONTROL 
 
11.4.3 Setting the required parameters for manual pulse generator operation 
The "Parameters" must be set to carry out manual pulse generator operation. 
The following table shows the setting items of the required parameters for carrying out 
manual pulse generator operation. When only manual pulse generator operation will 
be carried out, no parameters other than those shown below need to be set.    (Use the 
initial values or setting values within a range where no error occurs for trouble-free 
operation.)  
 
Setting item 
Setting requirement
Factory-set initial value 
(setting details) 
Param
eters
 
 Pr.1   Unit setting 
3 (pulse) 
 Pr.2   No. of pulses per rotation (Ap) (Unit: pulse) 
20000 
 Pr.3   Movement amount per rotation (Al) (Unit: pulse) 
20000 
 Pr.4   Unit magnification (Am) 
1 (1-fold) 
 Pr.5   Pulse output mode 
1 (CW/CCW mode) 
 Pr.6   Rotation direction setting 
 
0 (current value increases by 
forward run pulse output) 
 Pr.11   Backlash compensation amount (Unit: pulse) 
 Pr.12   Software stroke limit upper limit value (Unit: pulse) 
2147483647 
 Pr.13   Software stroke limit lower limit value (Unit: pulse) 
–2147483648 
 Pr.14   Software stroke limit selection 
0 (current feed value) 
 Pr.15   Software stroke limit valid/invalid setting 
0 (valid) 
 Pr.17   Torque limit setting value (Unit: %) 
300 
 Pr.22   Input signal logic selection 
 
0 (Manual pulse generator 
input is negative logic.) 
 Pr.23   Output signal logic selection   
 
0 (Pulse output to drive unit is 
negative logic.) 
 Pr.24   Manual pulse generator input selection   
 
0 (4 times multiplication of A 
phase/B phase) 
 
  :  Setting always required.   
  :  Set according to requirements (Leave set to the initial value when not used.)   
 
REMARK 
 Parameter settings work in common for all control using the QD75. When carrying 
out other control ("major positioning control", "high-level positioning control", "OPR 
positioning control"), the respective setting items must also be matched and set.   
 Parameters are set for each axis. But   Pr.22   Manual pulse generator input logic 
(b8),   Pr.24   is set only for axis 1. (The setting for axes 2,3, and 4 is ignored.) 
   Refer to CHAPTER 5 "DATA USED FOR POSITIONING CONTROL" for setting 
details.