12 - 98 
MELSEC-Q
12   CONTROL SUB FUNCTIONS 
 
12.7.7 Pre-reading start function 
The "pre-reading start function" does not output pulses while the execution prohibition 
flag is ON if a positioning start request is given with the execution prohibition flag ON, 
and starts outputting pulses within 1.3ms (QD75P N/QD75D N) or 3ms 
(QD75P /QD75D ) after OFF of the execution prohibition flag is detected. The 
positioning start request is given when the axis is in a standby status, and the 
execution prohibition flag is turned OFF at the axis operating timing. This shortens the 
virtual start time. The QD75 normally takes 1.5 to 2.0ms (QD75P N/QD75D N) or 6 
to 7ms (QD75P /QD75D ) from when it receives a positioning start request until it 
starts pulse output (start time). Some systems often need the start time to be 
shortened. This "pre-reading start function" can improve the tact time of the system. 
 
The "pre-reading start function" will be explained below. 
  [1] Control details 
  [2] Control precautions 
  [3] Program examples 
 
[1] Control details 
The pre-reading start function is performed by turning ON the positioning start 
signal [Y10, Y11, Y12, Y13] with the execution prohibition flag [Y14, Y15, Y16, 
Y17] ON, or by executing the dedicated instruction (ZP.PSTRT1, ZP.PSTRT2, 
ZP.PSTRT3, ZP.PSTRT4). However, if positioning is started with the execution 
prohibition flag ON, the positioning data is analyzed but pulse output is not 
provided. While the execution prohibition flag is ON, "   Md.26   Axis operation 
status" remains unchanged from "5: Analyzing". Pulse output starts within 1.3ms 
(QD75P N/QD75D N) or 3ms (QD75P /QD75D ) after the execution 
prohibition flag [Y14, Y15, Y16, Y17] has turned OFF, and "   Md.26   Axis 
operation status" changes to the status (e.g. "Position control", "Speed control") 
that matches the control system. (Refer to Fig. 12.52) 
 
V
ON
OFF
OFF
OFF
ON
ON
t
Ta
OFF
ON
ON
Positioning start 
signal
[Y10,Y11,Y12,Y13]
Execution 
prohibition flag
[Y14,Y15,Y16,Y17]
BUSY signal
[XC,XD,XE,XF]
Md.26 Axis operation 
status
Position control
Position control
Standby
Positioning 
data analysis
Execution prohibition flag 
OFF waiting
Analyzing
Positioning start timing 
Start time
1.3ms or less (QD75P   N/QD75D   N) or 
3ms or less(QD75P   /QD75D   )
 
Fig. 12.52 Operations of pre-reading start function