12   CONTROL SUB FUNCTIONS
12.2.2 OP shift function
When a machine OPR is carried out, the OP is normally established using the near-
point dog, stopper, and zero signal. However, by using the OP shift function, the
machine can be moved a designated movement amount from the position where the
zero signal was detected. A mechanically established OP can then be interpreted at
that point.
The OP shift function can be used without relation to "
Pr.43
 OPR method".
The details shown below explain about the "OP shift function".
  [1] Control details
  [2] Setting range for the OP shift amount
  [3] Movement speed during OP shift
  [4] Precautions during control
  [5] Setting the OP shift function
[1]   Control details
The following drawing shows the operation of the OP shift function.
Machine OPR start 
Pr.53 OP shift amount 
Speed selected by the " Pr. 56
Speed designation during OP 
shift"
Pr.47  Creep speed
Shift operation carried out after
the deviation counter clear and reset. 
Pr. 44  OPR direction 
Near-point dog
Pr. 46 OPR speed 
Zero signal 
Fig. 12.4 OP shift operation