FX Series Programmable Controller
Diagnostic Devices 6
6-9
For symbol key see page 6-1.
Please see the following page for the notes referenced in this table.
6.8
Link And Special Operation
Devices (M8070 to M8099 and D8070 to D8099) 
For symbol key see page 6-1.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8070 (
R)
Driven when the PLC is a 
master station in a parallel 
link application
D8070 (
)
Parallel link watchdog time - 
500 msec
M8071 (
R)
Driven when the PLC is a 
slave station in a parallel 
link application
D8071 - D8098 Reserved
M8072 (
)
ON while the PLC is operat-
ing in a parallel link
M8073 (
)
ON when M8070/ M8071 
are incorrectly set during 
parallel link operations
M8074
(FX
(2C)
 only)
Activate RAM file registers
M8075 -M8098
Reserved
M8099 (
)
High speed free timer oper-
ation
D8099
Free ring timer, range: 0 to 
32,767 in units of 0.1 msec 
(for use in measuring input 
pulse durations)
Note 3:
If the unit or block corresponding to a programmed 
I / O number is not actually loaded, M8060 is set to 
ON and the first device number of the erroneous 
block is written to D8060.
2
0
0
1
Device number:
10 to 177
Device type:
1 - Input X
0 - Output Y
= X 20
Contents of
D8060
Note 4:
An I/O bus check is executed when M8069 is 
turned ON. If an error occurs, error code 6103 or 
6104 is written to D8069 and M8061 is turned ON.
General note:
HPP refers to Handy programming panel.
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)