Справочник Пользователя для Mitsubishi Electronics FX2NC

Скачать
Страница из 382
PLC Device Tables 8
8-1
8.
PLC Device Tables
8.1
Performance Specification Of The FX
0
 And FX
0S
 
continued over the page....
Item
Specification
Remarks
Operation control method
Cyclic operation by stored program
I/O control method
Batch processing method (when 
END instruction is executed)
I/O refresh instruction is available
Operation processing time
Basic instructions: 1.6 to 3.6 
µ
s
Applied instructions: several 10’s to 100 
µ
s
Programming language
Relay symbolic language + step 
ladder
Step ladder can be used to pro-
duce an SFC style program
Program capacity
800 steps
Provided by built in EEPROM 
memory
Number of instructions
Basic sequence instructions: 20
Step ladder instructions: 2
Applied instructions: 35
A Maximum 50 applied instructions 
are available including all varia-
tions
I/O configuration
Max total I/O set by Main Processing Unit
Auxiliary
relay
(M coils)
General
512 points
M0 to M511
Latched
16 points (subset)
 M496 to M511
Special
56 points
From the range M8000 to M8255
State relays
(S coils)
General
64 points
S0 to S63
Initial
10 points (subset)
S0 to S9
Timers (T)
100 msec
Range: 0 to 3,276.7 sec
56 points
T0 to T55
10 msec
 Range: 0 to 327.67 sec
24 points
T32 to T55 when special M coil 
M8028 is driven ON
Counters (C)
General
Range: 1 to 32,767 counts
16 points
C0 to C13
Type: 16 bit up counter
Latched
2 points(subset)
C14 to C15
Type: 16 bit up counter
High speed
counters (C)
1 phase
Range: -2,147,483,648 to 
+2,147,483,647 counts
FX0: Select upto four 1 phase 
counters with a combined counting 
frequency of 5kHz or less.
Alternatively select one 2 phase or 
A/B phase counter with a counting 
frequency of 2kHz or less.
FX0S: When multiple 1-phase 
counters are used the sum of the 
frequencies must be equal or less 
than 14kHz. Only 1, 2 phase high 
speed counter may be used at any 
one time. When 2 phase counters 
are in use the maximum counted 
speeds must be equal or less than 
14kHz, calculated as (2 ph counter 
speed 5 number of counted edges) 
+ 1 ph counter speeds.
C235 to C238
(note C235 is latched)
4 points
1 phase
c/w start
stop input
C241(latched), C242 and C244 
(latched) 3 points
2 phase
C246, C247 and C249 (all latched) 
3 points
A/B phase
C251, C252 and C254 (all latched) 
3 points
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
FX Series Programmable Controllers