FX Series Programmable Controllers
Devices in Detail 4
4-5
4.3.3
Special Diagnostic Auxiliary Relays
A PLC has a number of special auxiliary relays. These relays all have specific functions and
are classified into the following two types.
a) Using contacts of special auxiliary relays
-
Coils are driven automatically  by the PLC. Only the contacts of these coils may be
used by a user defined program.
Examples: M8000: RUN monitor (ON during run)
M8002: Initial pulse (Turned ON momentarily when PLC starts)
M8012: 100 msec clock pulse
b) Driving coils of special auxiliary relays
-
A PLC executes a predetermined specific operation when these coils are driven by the
user.
Examples: M8033: All output statuses are retained when PLC operation is stopped
M8034: All outputs are disabled
M8039: The PLC operates under constant scan mode
4.3.4
Special Single Operation Pulse Relays
When used with the pulse contacts LDP, LDF, etc., M devices in the range M2800 to M3072
have a special meaning. With these devices, only the next pulse contact instruction after the
device coil is activated.
Available devices:
Not all PLC’s share the same range, quantity or operational meaning of diagnostic 
auxiliary relays. Please check the availability and function before using any device.
PLC specific diagnostic ranges and meanings are available in chapter 6.
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
M0
M0
M0
M0
SET
M50
X0
SET
M51
SET
M52
SET
M53
M0
LDP
LDP
LDP
LD
1
4
3
2
M2800
M2800
M2800
M2800
X0
SET
M52
SET
M50
SET
M53
M2800
LDP
LDP
LDP
LD
5
8
7
6
SET
M51
M2800 to M3072
M0 to M2799
Turning ON X0 causes M0 to turn ON.
Contacts 
 and 
 are pulse con-
tacts and activate for 1 scan.
Contact 
 is a normal LD contact and
activates while M0 is ON.
Turning ON X0 causes M2800 to turn ON.
Contact 
 is a pulse contact and acti-
vates for 1 scan.
Contacts 
 and 
 are pulse contacts
of the same M device as contact 
.
Contact 
 has already operated, so
contact 
 and 
 do not operate.
Contact 
 is a normal LD contact and
activates while M2800 is ON.