EOCR-i3BZ/iFBZ/3BZ2/FBZ2
EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,
EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT
Item 
Operating Condition & Setting Range 
Operation Time
Over Current (oc)
Load current(In) exceeds threshold(Is)
Definite(Def) : 0.2~30s Adjustable
Setting Range : 0.5~80A(Def), 0.5~32A(Inv & th)
Inverse(Inv) & Thermal(th) : 1~30 Class
Under Current (uc)
Load current(In) less than threshold(uc) In <= uc
oFF, 1~30s Adjustable
uc should be less than oc Setting
Phase Loss (PL) 
max imbalance is more than 85% among 3 phase current,
oFF, 0.5~5s Adjustable
Enable or disable : Selectable
Reverse Phase(rP)
Reversed phase sequence input on EOCR.
Within 0.15s
Enable or disable : Selectable
Active only in motor starting, In 
Stall threshold (Sc
×
OC).
Stall (Sc)
Setting Range : Adjustable
Immediately after D-Time elapsed
2~8 times of oc setting if Sc
×
OC doesn
t exceed 250A
Active only in motor running, In 
Jam threshold (JA
×
OC).
Jam (JA)
Setting Range : 
0.2~10s Adjustable
1.5~8 times of oc setting if JA
×
OC doesn
t exceed 250A
Current unbalance 
threshold1~10s Adjustable.
Unbalance (ub)
Setting Range : 10~50%
1~10s Adjustable
Unbalance[%] = 100 
×
(Max phase current 
-
Min phase current)/
Max phase current
Earth Fault (EF)
EF current(Ie) exceeds threshold(Ies)
0.1~10s Adjustable
Setting Range : oFF, 0.03~10A
Protection functions
Password 
Secure configuration, available only with i3BZ/iFBZ
Communication 
Serial network communication for monitoring of metering, status, and fault history
Fail Safe 
Enable/Disable fail-safe operation of OL trip output
Phase selection 
Select a Single-phase motor or 3-Phase motor
Total Running-Hour 
Record of total running from installation which cannot be modified or cleared
Running-Hour 
Accumulated running hour from preset point which can be cleared to zero, when motor stops
Fault History 
Records for recent 3 faults each phase current which stored in a non-volatile memory
Limitation of autoreset attempt
Block auto-reset if the reset count exceeds the pre-set count within 30 minutes
Auxillary functions
Item
Setting Remark
Protocol type 
Modbus RTU 
Communication type
RS-485  
Baud rate 
1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kbps 
Maximum length of the bus 
Maximum 1.2kM
Depend on the environment
Type of trunk cable
RS-485 Shielded Twist 2-Pair Cable   
Communication function (Applicable to i3BZ/iFBZ)