Справочник Пользователя для Mitsubishi Electronics FR-D720-008

Скачать
Страница из 294
158
Misoperation prevention and parameter setting restriction
4.17 Misoperation prevention and parameter setting restriction
4.17.1 Reset selection/disconnected PU detection/PU stop selection (Pr. 75)
(1) Reset selection
You can select the enable condition of reset function (RES signal, reset command through communication) input.
When Pr. 75  is set to any of "1, 3, 15, 17", a reset can be input only when the inverter is tripped.
(2) Disconnected PU detection
This function detects that the PU (FR-PU04/FR-PU07) has been disconnected from the inverter for longer than 1s and
causes the inverter to provide a fault output (E.PUE) and come to trip.
When Pr. 75 is set to any of "0, 1, 14, 15", operation is continued even if the PU is disconnected.
Purpose
Parameter that should be Set
Refer to Page
Limits reset function
Trips when PU is disconnected
Stops from PU
Reset selection/disconnected PU 
detection/PU stop selection
Pr. 75
Prevention of parameter rewrite
Parameter write disable selection
Pr. 77
Prevention of reverse rotation of the motor
Reverse rotation prevention selection
Pr. 78
Displays necessary parameters
Display of applied parameters 
Pr. 160
Parameter restriction with using 
password
Password function
Pr. 296, Pr. 297
Control of parameter write by 
communication
EEPROM write selection
Pr. 342
You can select the reset input acceptance, disconnected PU (FR-PU04/FR-PU07) connector detection function and PU
stop function.
Parameter 
Number
Name
Initial Value
Setting Range
Description
75
Reset selection/
disconnected PU detection/
PU stop selection
14
0 to 3, 14 to 17
For the initial value, reset always enabled, 
without disconnected PU detection, and 
with PU stop function.
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
The Pr. 75  value can be set any time. Also, if parameter (all) clear is executed, this setting will not return to the initial value.
Pr. 75
Setting
Reset Selection
Disconnected PU Detection
PU Stop Selection
0
Reset input normally enabled
When the PU is disconnected,
operation is continued.
Pressing 
 decelerates the motor
to a stop only in the PU operation
mode.
1
Reset input is enabled only when the fault
occurs.
2
Reset input normally enabled
When the PU is disconnected, the
inverter trips.
3
Reset input is enabled only when the fault
occurs.
14
(initial value)
Reset input normally enabled
When the PU is disconnected,
operation is continued.
Pressing 
decelerates the motor
to a stop in any of the PU, external
and communication operation modes.
15
Reset input is enabled only when the fault
occurs.
16
Reset input normally enabled
When the PU is disconnected, the
inverter trips.
17
Reset input is enabled only when the fault
occurs.
NOTE
When the reset signal (RES) is input during operation, the motor coasts since the inverter being reset shuts off the output. 
When reset is performed, cumulative values of electronic thermal O/L relay, and regenerative brake duty are cleared.
The reset key of the PU is only valid when the inverter is tripped, independently of the 
Pr. 75  setting.
REMARKS
When the PU has been disconnected since before power-on, it is not judged as a fault.
To make a restart, confirm that the PU is connected and then reset the inverter.
The motor decelerates to a stop when the PU is disconnected during PU Jog operation with Pr. 75 set to any of "0, 1, 14, 15"
(which selects operation to be continued if the PU is disconnected).
When RS-485 communication operation is performed through the PU connector, the reset selection/PU stop selection function
is valid but the disconnected PU detection function is invalid.