228
Useful functions
4.21 Useful functions
4.21.1 Cooling fan operation selection (Pr. 244)
In either of the following cases, fan operation is regarded as faulty as [FN] is shown on the operation panel, and the fan fault
(FAN) and alarm (LF) signals are output.
 Pr. 244 = "0"
 When the fan comes to a stop with power on.
Pr. 244 = "1"
 When the inverter is running and the fan stops during fan ON command.
For the terminal used for FAN signal output, set "25 (positive logic) or 125 (negative logic)" to Pr. 190 or Pr. 192 (output
terminal function selection)
, and for the LF signal, set "98 (positive logic) or 198 (negative logic)".
Purpose
Parameter that should be Set
Refer to Page
To increase cooling fan life
Cooling fan operation 
selection
Pr. 244
To determine the maintenance time 
of parts
Inverter part life display
 Pr. 255 to Pr. 259
Maintenance output 
function
 Pr. 503, Pr. 504
Current average value 
monitor signal
 Pr. 555 to Pr. 557
Freely available parameter
Free parameter
Pr. 888, Pr. 889
You can control the operation of the cooling fan (FR-D720-070 or more, FR-D740-036 or more, FR-D720S-070 or
more) built in the inverter.
Parameter 
Number
Name
Initial Value
Setting Range
Description
244
Cooling fan operation 
selection
1
0
Operates in power-on status.
Cooling fan ON/OFF control invalid (the
cooling fan is always on at power-on)
1
Cooling fan ON/OFF control valid
The fan is always on while the inverter is
running. During a stop, the inverter status
is monitored and the fan switches ON/
OFF according to the temperature.
The above parameter can be set when Pr.160 Extended function display selection = "0". (Refer to page 162)
NOTE
Changing the terminal assignment using Pr. 190, Pr. 192 (output terminal function selection) may affect the other functions.
Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)