4.21.4 Current average value monitor signal (Pr. 555 to Pr. 557)
 The pulse output of the current average value monitor signal (Y93) is shown above.
 For the terminal used for the Y93 signal output, assign the function by setting "93" (positive logic) or "193" (negative logic)
to Pr. 190 RUN terminal function selection. The function can not be assigned to Pr. 192 A,B,C terminal function selection.
1)  Setting of Pr. 556 Data output mask time
The output current is unstable (transient state) right after the operation is changed from the acceleration/deceleration state
to the constant speed operation. Set the time for not obtaining (mask) transient state data in Pr. 556.
2)  Setting of Pr. 555 Current average time 
The average output current is calculated during Hi output of start pulse (1s). Set the time taken to average the current
during start bit output in Pr. 555.
The average value of the output current during
constant speed operation and the maintenance timer
value are output as a pulse to the current average
value monitor signal (Y93).
The pulse width output to the I/O module of the
programmable controller or the like can be used as a
guideline to know abrasion of machines, elongation of
belt and the maintenance time for aged deterioration
of devices.
The current average value monitor signal (Y93) is
output as pulse for 20s as 1 cycle and repeatedly
output during constant speed operation.
Parameter 
Number
Name
Initial Value
Setting Range
Description
555
Current average time
1s
0.1 to 1s
Time taken to average the current during start pulse
output (1s).
556
Data output mask time
0s
0 to 20s
Time for not obtaining (mask) transient state data.
557
Current average value 
monitor signal output 
reference current
Rated 
inverter 
current
0 to 500A
Reference (100%) for outputting the signal of the
current average value.
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
Programmable controller
Output unit
Input unit
Maintenance  
time
Parts have  
reached their life
Inverter
Output current average value (A)
1) Data output mask time
When the speed has changed to 
constant from acceleration/deceleration, 
Y93 signal is not output for 
Pr. 556 time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
Output  current set in 
Pr. 555 time is averaged
3) Output current average value pulse
The averaged current value is output for 0.5 to 9s 
(10 to 180%) during start bit output.
Signal output time =
Pr. 557 (A)
4) Maintenance timer pulse
The maintenance timer value (
Pr. 503) is 
output as Hi pulse shape for 2 to 9s 
(16000h to 72000h)
Signal output time =
40000h
5) End pulse
Output as low pulse 
shape for 1 to 16.5s
Time
Y93 signal
1 cycle (20s)
Next cycle
Output frequency
From acceleration to constant speed operation
Pr. 503   100h
   5s
   5s