Справочник Пользователя для Mitsubishi Electronics FR-D720-008

Скачать
Страница из 294
Parameter list
Parameter list
56
Parameter List
4.2 Parameter list
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. For details of parameters, refer to the instruction manual.
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(Refer to page 183 for RS-485 communication)
" " indicates valid and "
×" indicates invalid of "control mode-based correspondence table", "parameter copy", "parameter clear", and "all parameter clear". 
Func-
tion
Parameter
Name
Setting Range
Minimum 
Setting 
Increments
Initial 
Value
Refer 
to 
Page  
Customer 
Setting
Parameter
Remarks
Instruction Code
Control Mode-based 
Correspondence Table
Parameter
Read
Write
Extended
Copy
Clear
All clear
Basic functions
 0
Torque boost
0 to 30%
0.1%
6/4/3% 
 0
00
80
0
×
 1
Maximum frequency
0 to 120Hz
0.01Hz
120Hz
 1
01
81
0
 2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
 2
02
82
0
 3
Base frequency
0 to 400Hz
0.01Hz
60Hz
 3
03
83
0
×
 4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
 4
04
84
0
 5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
 5
05
85
0
 6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
 6
06
86
0
 7
Acceleration time
0 to 3600s
0.1s
5/10s
 
 7
07
87
0
 8
Deceleration time
0 to 3600s
0.1s
5/10s
 
 8
08
88
0
 9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated 
inverter 
current
 9
09
89
0
D
C
 in
jec
tio
bra
ke
10
DC injection brake operation frequency 0 to 120Hz
0.01Hz
3Hz
10
0A
8A
0
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
12
DC injection brake operation voltage
0 to 30%
0.1%
6/4%
 
12
0C
8C
0
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
13
0D
8D
0
14
Load pattern selection
0 to 3
1
0
14
0E
8E
0
×
JO
G
opera
tion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
15
0F
8F
0
16
Jog acceleration/deceleration time
0 to 3600s
0.1s
0.5s
16
10
90
0
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120Hz
18
12
92
0
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
19
13
93
0
×
Accel
erati
on/
deceleration time
20
Acceleration/deceleration reference 
frequency
1 to 400Hz
0.01Hz
60Hz
20
14
94
0
St
al
l
pr
evention
22
Stall prevention operation level
0 to 200%
0.1%
150%
22
16
96
0
23
Stall prevention operation level 
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
23
17
97
0
Multi-
sp
eed 
setting
24
Multi-speed setting (speed 4)
0 to 400Hz, 9999
0.01Hz
9999
24
18
98
0
25
Multi-speed setting (speed 5)
0 to 400Hz, 9999
0.01Hz
9999
25
19
99
0
26
Multi-speed setting (speed 6)
0 to 400Hz, 9999
0.01Hz
9999
26
1A
9A
0
27
Multi-speed setting (speed 7)
0 to 400Hz, 9999
0.01Hz
9999
27
1B
9B
0
29
Acceleration/deceleration pattern 
selection
0, 1, 2
1
0
29
1D
9D
0
REMARKS
 indicates simple mode parameters.
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
V/F
V/F
V/F
GP MFVC
GP MFVC
GP MFVC