Features
Standard 
Specifications
Outline Dimension 
Drawings
Terminal Connection 
Diagram
Terminal Specification 
Explanation
Explanation of the 
Operation Panel
(FR-DU07)
Parameter List
Explanations of 
Parameters
Protective Functions
Option and 
Peripheral Devices
Precautions for 
Operation/Selection
Precautions for Peripheral 
Device Selection
Application to Motor
Warranty
Main differences and 
compatibilities with 
the FR-F500(L) series
International FA center
Connection with 
Peripheral Devices
Why can the inverter 
save energy?
1
5
7
9
16
19
21
28
47
49
59
63
64
65
66
(1)
 Adjustable 
5 points
 V/F
2
1
Evolution of the inverter for fan and pump applications,    energy savings for buildings and factories as a whole
Evolution of the inverter for fan and pump applications,    energy savings for buildings and factories as a whole
[Ex. of Blower Operation Characteristics]
[Ratio of Motor Power Consumption during Acc./Dec.]
•Achieved a higher level of energy savings during acc./dec. to say 
nothing of during constant speed.
FR-F700
Conventional model
(FR-F500)
Motor Lord Torque (%)
(1)
 Upgrade of the renown Optimum Excitation Control!!
•The effect of energy savings can be confirmed using the 
operation panel, output terminal (FM, AM terminal) and 
via networks with the newly developed energy saving 
monitor.
(2)
 The effect of energy savings is obvious
Ex. of Power Savings 
Monitor Display
[Energy Saving Monitor List]
Power saving monitor (kW)
Power saving rate (%)
Power saving amount (kWh)
Power saving amount charge ($)
Power saving average value (kW)
Power saving rate average value (%)
Power saving charge average value ($)
Annual power saving amount (kWh)
Annual power saving amount charge ($)
0
10
20
30
40
50
100
90
M
O
RE
SAVIN
G
S
!
Driving of the Mitsubishi 400V 4 poles 
45kW motors comparison
12%
Commercial 
power 
operation
Frequency (Hz)
V/F control
0
10
20
30
40
50
60
20
40
60
80
100
Optimum 
excitation 
control
6%
Power Consumption (%)
Power Consumption Ratio (%)
A
Photo:FR-F740-5.5K
RS-485 terminal
Combed shaped wiring cover
Removable terminal block
Easy operation 
with the setting 
dial of the 
operation panel
Built-in
 EMC filter
AU/PTC 
switchover switch
Connector 
with/without
 EMC filter
RS-485 communication is 
possible with PU connector
Easy replacement with
the cooling fan cassette!!
E
G
C
H
A
B
D
F
BEST 
MATCH
•Possible to set the torque 
pattern that is optimum for the 
machine's characteristic
•Possible to expect even more 
energy savings with optimum 
excitation control and optimum 
V/F pattern working together
0
V/F5
V/F4
V/F3
V/F2
V/F1
Voltage
Base
Frequency
V/F Characteristic
Torque 
characteristic 
curves
V/F 
pattern
Frequency
Base 
Frequency 
Vo
ltage
(2)
 Enhanced PID function
•Energy savings in low speed region ... PID shutoff (sleep control) function
•Shorter PID startup time ... PID automatic switchover function
•Monitor of set point/measured value/deviation possible ... PID monitor
•Convenient for HVAC usage ... forward/reverse operation switchover 
is simple with an external signal
•Corresponds to a wide range of detectors ... set point and measured value 
for PID input can either be voltage (0 to 5V/0 to 10 V) or current (4 to 20mA)
(3)
 Adoption of the original operation continuation 
at instantaneous power failure function
•Operation continues without 
the motor coasting when an 
instantaneous power failure 
occurred in fan and blower 
applications.
*The inverter may trip and the motor may 
coast depending on the load condition.
IPF
Input 
Power Supply
Output 
Frequency
Deceleration
Reacceleration
When power is restored during deceleration
•Restart can be made without stopping the 
motor when the motor is coasting due to an 
instantaneous power failure.
(4)
 Restart after instantaneous 
power failure function
•Smoothly restarts a motor that is rotating even in 
the opposite direction due to the windmill effect.
(5)
 Flying start
•Possible to avoid regeneration overvoltage alarm by 
automatically increasing the frequency and continue 
operation if the fan happens to rotate faster due to 
the effect of another fan in the same duct.
(6)
 Regeneration avoidance function
•Switchover to commercial power-supply operation is 
simple using R1 and S1 terminals of the control circuit 
and commercial power-supply switchover sequence.
(8)
 Commercial power-supply 
switchover sequence
•Protection of the motor can be certain since the 
built-in PTC of the motor can be input directly in 
addition to the electronic thermal relay function.
PTC thermistor input…Positive Temperature Coefficient Thermistor
(7)
 PTC thermistor input
B
•Adoption of newly developed long life cooling fan 
(design life of 10 years*
1
)
Longer operating life is further enhanced with the use of ON/OFF control of cooling fan.
•Adoption of long life capacitor 
(design life of 10 years*
1, 2
)
A capacitor with specification of 5000 hours at 105˚C ambient temperature is adapted.
 
*1  Ambient temperature: yearly average 40˚C (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Since the design life is a calculated value, it is not a guaranteed value.
*2  Output current: 80% of the rated current of Mitsubishi standard 4P motor
(1)
 Operating life of parts are further lengthened
•Degrees of deterioration of main circuit capacitor, control circuit 
capacitor or inrush current limit circuit can be diagnosed by monitor.
•Trouble can be avoided with the self-diagnostic alarms* that is 
output when the life span is near.
*Any of alarm for main circuit capacitor, control circuit capacitor, inrush current limit 
circuit and cooling fan can be output.
(2)
 State of the art longevity diagnostic method
•Maintenance timer output function can also inform of 
maintenance time for peripheral equipments.
•Average output current value and maintenance timer value are output as pulses.
(3)
 Maintenance timer
(4)
 Update is also easy
¥
When exchanging the inverter, the control 
circuit terminals can be exchanged.
The removable terminal block of the FR-
F500 series can be used.
(The terminal block of the FR-F700 series is compatible with 
that of the FR-F500 series.
Note that some functions of the FR-F700 series are restricted 
when using the terminal block of the FR-F500 series.)
Removable terminal block
A
C
D
¥
Wiring cover can be reinstalled after wiring.
 (200V class 22K or less, 400V class 30K or less)
Wiring is easy with the combed shaped wiring cover
¥
Parameter setting for multiple inverters is simple by 
copy with the operation panel.
Possible to copy parameters with operation panel
(5)
 Improved workability
¥
The installation position of the cooling fan is in the 
upper portion of the inverter. 
Fan replacement is easily done without having to 
remove the main circuit wires.
Easy replacement of cooling fan
¥
Alarm history (alarm details and frequency, current, voltage 
and cumulative energization time at time of alarm 
occurrence) can be displayed on the operation panel and 
the cause of a trouble can be checked.(up to 8 past alarms)
Alarm history
FR-F500 series
FR-F700 series
RELIABLE
EASY
I