134
Position control by vector control
4.6.2
Simple position feed function by contact input (Pr. 419, Pr. 464 to Pr. 494) 
REMARKS
⋅ For the servo ON signal (LX), set "23" in Pr. 178 to Pr. 189 (input terminal function selection) to assign the function.
⋅ For the in-position signal (Y36), set "36" in Pr. 190 to Pr. 196 (output terminal function selection) to assign the function.
CAUTION
Changing the terminal function using any of Pr. 178 to Pr. 189, 190 to Pr. 196 may affect the other functions. Set parameters after
confirming the function of each terminal.
Parameters referred to
Pr. 178 to Pr. 189 (input terminal function selection) 
 Refer to page 231
Pr. 190 to Pr. 196 (output terminal function selection) 
 Refer to page 239 
Inputting the number of pulses (positions) in the parameters and setting multi-speed and forward (reverse)
commands enable position control. The motor does not return to the home position with this simple position feed
function.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
419
Position command source 
selection
0
0
Simple position control function by contact input. 
(position command by parameter settings)
1
Pulse train position command from the positioning 
module of the programmable controller system 
(when FR-A7AL is installed)
2
Simple pulse train position command by inverter 
pulse train input
464
Digital position control 
sudden stop deceleration 
time
0s
0 to 360.0s
Set the time until the inverter stops when the 
forward rotation (reverse rotation) command is 
turned OFF with the position feed forward function.
Selection Method
(OFF: ×, ON:  )
Position feed 
frequency
REX
RH
RM
RL
465
First position feed amount 
lower 4 digits
0
0 to 9999
×
×
×
High speed (Pr. 4)
466
First position feed amount 
upper 4 digits
0
0 to 9999
467
Second position feed 
amount lower 4 digits
0
0 to 9999
×
×
×
Middle speed (Pr. 5)
468
Second position feed 
amount upper 4 digits
0
0 to 9999
469
Third position feed 
amount lower 4 digits
0
0 to 9999
×
×
×
Low speed (Pr. 6)
470
Third position feed 
amount upper 4 digits
0
0 to 9999
471
Fourth position feed 
amount lower 4 digits
0
0 to 9999
×
×
4 speed (Pr. 24)
472
Fourth position feed 
amount upper 4 digits
0
0 to 9999
473
Fifth position feed amount 
lower 4 digits
0
0 to 9999
×
×
5 speed (Pr. 25)
474
Fifth position feed amount 
upper 4 digits
0
0 to 9999
475
Sixth position feed 
amount lower 4 digits
0
0 to 9999
×
×
6 speed (Pr. 26)
476
Sixth position feed 
amount upper 4 digits
0
0 to 9999
477
Seventh position feed 
amount lower 4 digits
0
0 to 9999
×
7 speed (Pr. 27)
478
Seventh position feed 
amount upper 4 digits
0
0 to 9999
Vector
Vector
Vector