Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
4
137
4.6.3
Position control (Pr. 419, Pr. 428 to Pr. 430) by inverter pulse train input 
(1) Operation
Turning ON the servo ON signal (LX) cancels the output shut-off and the operation ready signal (RDY) turns ON after
0.1s. Turning ON the STF (forward stroke end signal) or STR (forward stroke end signal) runs the motor according to
the commanded pulse. When the forward (reverse) stroke end signal turns OFF, the motor does not run in that
direction.
(2) Pulse train form type selection (Pr. 428, NP signal)
1) Set "2"(simple pulse train position command) in Pr. 419.
2) Set "68" in Pr. 178 to Pr. 189 (input terminal function selection) to assign simple position pulse train sign (NP).
3) Select command pulse train using Pr. 428
4)Select vector control, then select position control.
Simple position pulse train command can be input by pulse train input and sign signal (NP) to the JOG terminal. 
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
419
Position command source 
selection
0
0
Simple position control function by contact input. 
(position command by parameter settings)
1
Pulse train position command from the positioning 
module of the programmable controller system 
(when FR-A7AL is installed)
2
Simple pulse train position command by inverter 
pulse train input
428
Command pulse selection
0
0 to 2
Pulse train + rotation 
signal sign
Negative logic
3 to 5
Positive logic
429
Clear signal selection
1
0
Deviation counter is cleared at edge of turning ON 
of the clear signal (CLR) from OFF.
1
Deviation counter while the clear signal (CLR) is 
ON
430
Pulse monitor selection
9999
0 to 5
The status of various pulses during running is 
displayed.
9999
Frequency monitor is displayed.
The above parameters can be set when the FR-A7AP/FR-A7AL (option) is mounted.
Pr. 428 Setting
Command Pulse Train Type
At Forward Rotation
At Reverse Rotation
0 to 2
Negative 
logic
Pulse train + 
rotation signal sign
3 to 5
Positive 
logic
Pulse train + 
rotation signal sign
REMARKS
⋅ When  Pr. 419 Position command source selection = "2" (simple pulse train position command), JOG terminal serves as simple
position pulse train input terminal regardless of the Pr. 291 Pulse train I/O selection setting.
Vector
Vector
Vector
Actual rotation
Forward rotation
Reverse rotation
Base signal
Operation ready completion (RDY)
Forward stroke end (STF)
Reverse stroke end (STR)
Inverter pulse train command
Sign signal (NP)
In-position (Y36)
Servo on (LX)
0.1s
JOG
NP
H
L
JOG
NP
H
L