Motor brake and stop operation
4
4.14 Motor brake and stop operation
4.14.1 DC injection brake and zero speed control, servo lock (LX signal, X13 signal, 
Pr. 10 to Pr. 12, Pr. 802, Pr. 850)
* This parameter can be set when the FR-A7AP/FR-A7AL (option) is mounted.
............Specifications differ according to the date assembled. Refer to page 484  to check the SERIAL number.
Purpose
Parameter that must be Set
Refer to Page
Motor braking torque adjustment
DC injection brake and zero speed 
control, servo lock
Pr. 10 to Pr. 12, 
Pr. 802, Pr. 850
Improve the motor braking torque 
with an option
Selection of a regenerative brake
Pr. 30, Pr. 70
Performing operation by DC current 
input
DC current feeding mode
Pr. 30
Coast the motor to a stop
Selection of motor stopping method
Pr. 250
Used to stop the motor with a 
mechanical brake (vibration restraint 
at stop-on-contact)
Stop-on-contact control
Pr. 270, Pr. 275, 
Pr. 276
Used to stop the motor with a 
mechanical brake (operation timing 
of a mechanical brake)
Brake sequence function
Pr. 278 to Pr. 285,
 Pr. 292
Perform position stop (orientation) 
control of the rotation shaft
Orientation control
Pr. 350 to Pr. 366,
Pr. 369, Pr. 393, 
Pr. 396 to Pr. 399
The DC injection brake can be operated at a motor stop to adjust the stop timing and braking torque.
Zero speed control can be selected during Real sensorless vector control and either zero speed control or
servo lock can be selected under vector control.
In DC injection brake operation, DC voltage is directly applied to the motor to prevent the motor shaft from
rotating when a motor decelerates to stop. While, in zero speed control, vector control is performed to maintain
0r/min. In either control, the motor will not return to the original position if the motor shaft rotates due to
external force.
The motor shaft position is maintained with servo lock. The motor will return to the original position if the motor
shaft rotates due to external force.
Select the magnetic flux decay output shutoff function to decay the magnetic flux before shutting off the output
at a stop.
Parameter 
Number
Name
Initial Value
Setting Range
Description
10
DC injection brake 
operation frequency
3Hz
0 to 120Hz
Set the operation frequency of the DC 
injection brake (zero speed control, servo 
lock).
9999
Operated at Pr. 13 or less.
11
DC injection brake 
operation time
0.5s
0
DC injection brake (zero speed control) 
disabled
0.1 to 10s
Set the operation time of the DC injection 
brake (zero speed control, servo lock).
12
DC injection brake 
operation voltage
7.5K or lower
4%
0 to 30%
Set the DC injection brake voltage (torque). 
When "0" is set, DC injection brake is disabled.
11K to 55K
2%
75K or higher
1%
802 *
Pre-excitation 
selection
0
0
Zero speed control
1
Servo  lock
850
Brake operation 
selection
0
0
DC injection brake operation
1
Zero speed control (during Real sensorless 
vector control)
2
Magnetic flux decay output shutoff  (during 
Real sensorless vector control)