232
Function assignment of external terminal and control
(1) Input terminal function assignment
⋅ Use Pr. 178 to Pr. 189 to set the functions of the input terminals.
⋅ Refer to the following table and set the parameters:
Setting
Signal 
Name
Function
Related Parameters
Refer to 
Page
0
RL
Pr. 59 = 0 (initial value)
Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, 
Pr. 232 to Pr. 239
Pr. 59 = 1 to 3 
*1
Remote setting (setting clear)
Pr. 59
Pr. 270 = 1, 3, 11 or 13 
*2
Stop-on-contact selection 0
Pr. 270, Pr. 275, Pr. 276
1
RM
Pr. 59 = 0 (initial value)
Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, 
Pr. 232 to Pr. 239
Pr. 59 = 1 to 3 
*1
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59 = 0 (initial value)
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, 
Pr. 232 to Pr. 239
Pr. 59 = 1 to 3 
*1
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 51, Pr. 450 to Pr. 463, 
Pr. 569, Pr. 832, Pr. 836, etc.
Pr. 270 = 1, 3, 11 or 13 
*2
Stop-on-contact selection 1
Pr. 270, Pr. 275, Pr. 276
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Selection of automatic restart after instantaneous power failure, 
flying start
Pr. 57, Pr. 58, Pr.162 to Pr.165, 
Pr. 299, Pr. 611
Commercial power supply-inverter switchover function
Pr. 57, Pr. 58, Pr.135 to Pr.139, 
Pr. 159
7
OH
External thermal relay input 
*3
Pr. 9
8
REX
15-speed selection (combination with three speeds RL, RM, 
RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, 
Pr.232 to Pr.239
9
X9
Third function selection
Pr. 110 to Pr. 116
10
X10
Inverter run enable signal (FR-HC, MT-HC, FR-CV connection)
Pr. 30, Pr. 70
11
X11
FR-HC or MT-HC connection, instantaneous power failure detection Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
13
X13
External DC injection brake operation start
Pr. 10 to Pr. 12
14
X14
PID control valid terminal
Pr. 127 to Pr. 134, Pr. 575 to Pr. 577
15
BRI
Brake opening completion signal
Pr. 278 to Pr. 285
16
X16
PU/External operation switchover (turning ON X16 selects 
External operation)
Pr. 79, Pr. 340
17
X17
Load pattern selection forward/reverse rotation boost (turning ON 
X17 changes the output characteristics to constant torque load)
Pr. 14
18
X18
V/F switchover (V/F control is performed when X18 is on)
Pr. 80, Pr. 81, Pr. 800
19
X19
Load torque high-speed frequency
Pr. 270 to Pr. 274
20
X20
S-pattern acceleration/deceleration C switching terminal
Pr. 380 to Pr. 383
22
X22
Orientation command (for FR-A7AP/FR-A7AL) 
*4, *6
Pr. 350 to Pr. 369
23
LX
Pre-excitation/servo on 
*5
Pr. 850
24
MRS
Output stop
Pr. 17
Commercial power supply-inverter switchover function
Pr. 57, Pr. 58, Pr.135 to Pr.139, 
Pr. 159
25
STOP
Start self-holding selection
26
MC
Control mode changing
Pr. 800
27
TL
Torque limit selection
Pr. 815
28
X28
Start-time tuning start external input 
Pr. 95
42
X42
Torque bias selection 1 (for FR-A7AP/FR-A7AL)
 *6
Pr. 840 to Pr. 845
43
X43
Torque bias selection 2 (for FR-A7AP/FR-A7AL)
 *6
Pr. 840 to Pr. 845
44
X44
P/PI control switchover (turning ON X44 selects P control)
Pr. 820, Pr. 821, Pr. 830, Pr. 831
60
STF
Forward rotation command
(assigned to STF terminal (Pr. 178) only)
236
61
STR
Reverse rotation command
(assigned to STR terminal (Pr. 179) only)
62
RES
Inverter reset
63
PTC
PTC thermistor input (assigned to AU terminal (Pr. 184) only)
Pr. 9
64
X64
PID forward/reverse action switchover
Pr. 127 to Pr. 134, Pr. 5
65
X65
PU/NET operation switchover (turning ON X65 selects PU operation) Pr. 79, Pr. 340
66
X66
External/NET operation switchover (turning ON X66 selects 
NET operation)
Pr. 79, Pr. 340
67
X67
Command source switchover (turning ON X67 makes Pr. 338 
and Pr. 339 commands valid)
Pr. 338, Pr. 339
68
NP
Simple position pulse train sign (for FR-A7AP/FR-A7AL)
 *6
Pr. 291, Pr. 419 to Pr. 430, Pr. 464