Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
236
Function assignment of external terminal and control
4.15.4 Start signal operation selection (STF, STR, STOP signal, Pr. 250)
(1) 2-wire type (STF, STR signal)
⋅ A two-wire type connection is shown below.
⋅ In the initial setting, the forward/reverse rotation signals (STF/STR) are used as start and stop signals. Turn on
either of the forward and reverse rotation signals to start the motor in the corresponding direction. If both are turned
OFF (or on) during operation, the motor decelerates to a stop.
⋅ The speed setting signal may either be given by entering 0 to 10VDC across the speed setting input terminal 2-5,
by setting the required values in Pr. 4 to Pr. 6 Multi-speed setting (high, middle, low speeds), etc. (For multi-speed
operation, refer to page 165)
⋅ When Pr. 250 is set to any of "1000 to 1100, 8888", the STF signal becomes a start command and the STR signal a
forward/reverse command.
You can select the operation of the start signal (STF/STR).
You can select the stopping method (deceleration to a stop or coasting) when the start signal turns OFF.
You can stop the motor with a mechanical brake, etc. together with switching OFF of the start signal.
(Refer to page 213 for stop selection)
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
Start signal (STF/STR)
Stop operation
(Refer to page 213)
250
Stop selection
9999
0 to 100s
STF signal: Forward rotation 
start
STR signal: Reverse rotation 
start
The motor is coasted to a stop 
when the preset time elapses 
after the start signal is turned 
OFF. When the setting is any 
of 1000s to 1100s, the inverter 
coasts to a stop in (Pr. 250 - 
1000)s.
1000s to 
1100s
STF signal: Start signal
STR signal: Forward/reverse 
rotation signal
9999
STF signal: Forward rotation 
start
STR signal: Reverse rotation 
start
When the start signal is turned 
OFF, the motor decelerates to 
stop.
8888
STF signal: Start signal
STR signal: Forward/reverse 
rotation signal
2-wire connection example (Pr. 250 = "9999")
2-wire connection example (Pr. 250 = "8888")
REMARKS
⋅ When Pr. 250 is set to any of "0 to 100, 1000 to 1100", the motor coasts to a stop if the start command is turned OFF. (Refer to
page 213)
⋅ The STF and STR signals are assigned to the STF and STR terminals in the initial setting. The STF signal can be assigned to
Pr. 178 STF terminal function selection and the STR signal to Pr. 179 STR terminal function selection only.
Forward 
rotation start
Reverse 
rotation start
STF
ON
Time
STF
STR Inverter
Output frequency
ON
STR
10
2
5
Forward 
rotation
Reverse 
rotation
SD
Start signal
Forward/
reverse 
signal
STF
Time
STF
STR Inverter
Output frequency
STR
10
2
5
Forward 
rotation
Reverse 
rotation
ON
ON
SD