4.15.6 Output terminal function selection (Pr. 190 to Pr. 196)
.............Specifications differ according to the date assembled. Refer to page 484  to check the SERIAL number.
(1) Output signal list
⋅ You can set the functions of the output terminals.
⋅ Refer to the following table and set the parameters: (0 to 99: Positive logic, 100 to 199: Negative logic)
You can change the functions of the open collector output terminal and relay output terminal.
Parameter 
Number
Name
Initial 
Value
Initial signal
Setting Range
190
RUN terminal 
function selection
Open 
collector 
output 
terminal
0
RUN (inverter running)
0 to 8, 10 to 20, 25 to 28, 30 to 36, 
39, 41 to 47, 55, 64, 70, 83 to 85, 
90 to 99, 100 to 108, 110 to 116, 
120, 125 to 128, 130 to 136, 139, 
141 to 147, 155, 164, 170, 183 to 
185, 190 to 199, 9999 
191
SU terminal function 
selection
1
SU (up to frequency)
192
IPF terminal function 
selection
2
IPF (instantaneous power 
failure, undervoltage)
193
OL terminal function 
selection
3
OL (overload alarm)
194
FU terminal function 
selection
4
FU (output frequency 
detection)
195
ABC1 terminal 
function selection
Relay 
output 
terminal
99
ALM (fault output)
0 to 8, 10 to 20, 25 to 28, 30 to 36, 
39, 41 to 47, 55, 64, 70, 83 to 85, 
90, 91, 94 to 99, 100 to 108, 110 to 
116, 120, 125 to 128, 130 to 136, 
139, 141 to 147, 155, 164, 170, 183 
to 185, 190, 191, 194 to 199, 9999
196
ABC2 terminal 
function selection
9999
No function
Setting
Signal 
Name
Function
Operation
Related 
Parameters
Refer 
to Page
Positive 
Logic
Negative 
Logic
0
100
RUN
Inverter running
Output during operation when the inverter 
output frequency rises to or above Pr. 13 Starting 
frequency
.
-
1
101
SU
Up to frequency 
*1
Output when the output frequency is reached to 
the set frequency.
 
Pr. 41
2
102
IPF
Instantaneous power 
failure/undervoltage
Output at occurrence of an instantaneous power 
failure or when undervoltage protection is 
activated.
Pr. 57
3
103
OL
Overload alarm
Output while stall prevention function is 
activated.
Pr. 22, Pr. 23, 
Pr. 66, Pr. 148, 
Pr. 149, Pr. 154
4
104
FU
Output frequency 
detection 
Output when the output frequency reaches the 
frequency set in Pr. 42 (Pr. 43 for reverse 
rotation).
 
Pr. 42, Pr. 43
5
105
FU2
Second output 
frequency detection 
Output when the output frequency reaches the 
frequency set in Pr. 50.
 
Pr. 50
6
106
FU3
Third output frequency 
detection 
Output when the output frequency reaches the
frequency set in Pr. 116.
 
Pr. 116
7
107
RBP
Regenerative brake 
pre-alarm
Output when 85% of the regenerative brake 
duty set in Pr. 70 is reached.
Pr. 70
8
108
THP
Electronic thermal O/L 
relay pre-alarm
Output when the electronic thermal relay 
function cumulative value reaches 85% of the 
trip level.
(Electronic thermal relay function protection 
(E.THT/E.THM) activates, when the value 
reached 100%.)
Pr. 9
10
110
PU
PU operation mode
Output when the PU operation mode is 
selected.
Pr. 79
11
111
RY
Inverter operation 
ready
Output when the inverter power is turned ON, 
then output after reset process is completed 
(when the inverter can be started by switching 
the start signal ON or while it is running).
-
12
112
Y12
Output current 
detection
Output when the output current is higher than 
the Pr. 150 setting for longer than the time set in 
Pr. 151.
Pr. 150, Pr. 151