4.17 Operation selection at power failure and instantaneous 
power failure
4.17.1 Automatic restart after instantaneous power failure/flying start
(Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 299, Pr. 611)
Purpose
Parameter that must be Set
Refer to Page
At instantaneous power failure 
occurrence, restart inverter without 
stopping motor
Automatic restart operation 
after instantaneous power 
failure/flying start
Pr. 57,  Pr. 58,  Pr. 162 to Pr. 165, 
Pr. 299, Pr. 611
When undervoltage or a power 
failure occurs, the inverter can be 
decelerated to a stop.
Power failure-time 
deceleration-to-stop 
function
Pr. 261 to Pr. 266, Pr. 294
You can restart the inverter without stopping the motor in the following cases.
⋅ when commercial power supply operation is switched to inverter operation
⋅ when power comes back ON after an instantaneous power failure
⋅ when motor is coasting at start
Parameter 
Number
Name
Initial Value
Setting Range
Description
57
Restart coasting 
time
9999
0
⋅ 1.5K or lower .................................................... 0.5s,
⋅ 2.2K to 7.5K
.................................................
1s,
⋅ 11K to 55K
...................................................
3.0s,
⋅ 75K or higher .................................................... 5.0s,
The above times are coasting time.
55K or 
lower
0.1 to 
5s
Set the waiting time for inverter-triggered restart after 
an instantaneous power failure.
75K or 
higher
0.1 to 
30s
9999
No restart
58
Restart cushion 
time
1s
0 to 60s
Set a voltage starting time at restart.
162
Automatic restart 
after 
instantaneous 
power failure 
selection
0
0
With frequency search
1
Without frequency search (reduced voltage system)
2
Encoder detection frequency search
10
Frequency search at every start
11
Reduced voltage system at every start
12
Encoder detection frequency search at every start
163
First cushion time 
for restart
0s
0 to 20s
Set a voltage starting time at restart.
Consider using these parameters according to the load 
(moment of inertia, torque) magnitude.
164
First cushion 
voltage for restart
0%
0 to 100%
165
Stall prevention 
operation level for 
restart
150%
0 to 220%
Consider the rated inverter current as 100% and set the 
stall prevention operation level during restart operation.
299
Rotation direction 
detection 
selection at 
restarting
0
0
Without rotation direction detection
1
With rotation direction detection
9999
When Pr. 78 = "0", the rotation direction is detected.
When Pr. 78 = "1","2", the rotation direction is not detected.
611
Acceleration time 
at a restart
55K 
or lower
5s
0 to 3600s, 9999
Set the acceleration time that takes to reach Pr. 20 
Acceleration/deceleration reference frequency
 setting at a 
restart. 
Acceleration time for restart is the normal acceleration 
time (e.g. Pr. 7 ) when "9999" is set.
75K 
or higher
15s