Energy saving operation and energy saving monitor
(1) Energy saving monitor list
⋅ The following provides the items that can be monitored by the power saving monitor (Pr. 52, Pr. 54, Pr. 158 = "50"). 
(Only 1) power saving and 3) power saving average value can be output to Pr. 54 (terminal FM) and Pr. 158
(terminal AM))
⋅ The following shows the items which can be monitored by the cumulative saving power monitor (Pr. 52 = "51").
(The monitor value of the cumulative monitor can be shifted to the right with Pr. 891 Cumulative power monitor digit
shifted times
.)
Energy Saving 
Monitor Item
Description and Formula
Incre-
ments
Parameter Setting
Pr. 895 Pr. 896 Pr. 897 Pr. 899
1)
Power saving
Difference between the estimated value of power 
necessary for commercial power supply operation 
and the input power calculated by the inverter
Power during commercial power supply 
operation 
 input power monitor
0.01kW/
0.1kW 
9999
9999
2)
Power saving rate
Ratio of power saving on the assumption that power 
during commercial power supply operation is 100%
 × 100
0.1%
0
Ratio of power saving on the assumption that Pr. 
893
 is 100%
 × 100
1
3)
Power saving 
average value
Average value of power saving amount per hour 
during predetermined time (Pr. 897)
0.01kWh
/0.1kWh 
9999
9999
0 to 
1000h
4)
Power saving rate 
average value
Ratio of power saving average value on the 
assumption that the value during commercial 
power supply operation is 100%
 × 100
0.1%
0
Ratio of power saving average value on the 
assumption that Pr. 893 is 100%
 × 100
1
5)
Average power cost 
savings
Power saving average value represented in terms 
of cost
3) Power saving average value 
× Pr. 896
0.01/0.1 
0 to 
500
Energy Saving 
Monitor Item
Description and Formula
Incre-
ments
Parameter Setting
Pr. 895 Pr. 896 Pr. 897 Pr. 899
6)
Power saving 
amount
Power saving is added up per hour.
Σ (  1) Power saving × Δt)
0.01kWh
/0.1kWh
*1*2*3
9999
9999
7)
Power cost 
savings
Power saving amount represented in terms of cost
6) Power saving amount 
× Pr. 896
0.01/0.1
 
*1*3
0 to 
500
8)
Annual power 
saving amount
Estimated value of annual power saving amount
 × 24 × 365 × 
0.01kWh
/0.1kWh
 
9999
0 to 
100%
9)
Annual power 
cost savings
Annual power saving amount represented in terms of 
cost
8) Annual power saving amount 
× Pr. 896
0.01/0.1
 
*1*3
0 to 
500
*1
For communication (RS-485 communication, communication option), the display increments are 1. For example, the communication data is
"10" for "10.00kWh".
*2
When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
*3
The setting depends on capacities. (55K or lower/75K or higher)
REMARKS
⋅ As the operation panel (FR-DU07) is 4-digit display, it displays in 0.1 increments since a carry occurs, e.g. "100.0", when a
monitor value in 0.01 increments exceeds "99.99". The maximum display is "9999".
⋅ As the operation panel (FR-PU04/FR-PU07) is 5-digit display, it displays in 0.1 increments since a carry occurs, e.g. "1000.0",
when a monitor value in 0.01 increments exceeds "999.99". The maximum display is "99999".
⋅ The upper limit of communication (RS-485 communication, communication option) is "65535" when Pr. 898 Power saving
cumulative monitor clear = "9999". The upper limit of 0.01 increments monitor is "655.35" and that of 0.1 increments monitor is
"6553.5".
Power during commercial 
power supply operation
1) Power saving
1) Power saving
Pr. 893
Σ (  1) Power saving × Δt)
Pr. 897
Σ (  2) Power saving rate × Δt)
Pr. 897
3) Power saving average value
Pr. 893
6) Power saving amount
Operation time during accumulation 
of power saving amount
Pr. 899
100