303
4
b) Method to adjust any point without application of a voltage (current) across terminals 1 and 5(4 and 5)
(To change from 8V (80%) to 10V (100%))
REMARKS
You can check the current torque setting bias/gain setting by pressing 
after step 6.
You cannot check after performing operation in step 7.
1. 
Confirm the RUN indicator and operation mode 
indicator. 
    The inverter must be at a stop. 
    The inverter must be in the PU operation 
    mode. (Using        )
Display
Operation
Analog voltage (current) 
value (%) across terminals 1 and 5 
(across terminals 4 and 5)
The gain torque is 
reached when the analog 
voltage (current) value across 
terminals 1 and 5 (across terminals
4 and 5) is 100%.
Flicker...Parameter setting complete!!
(Adjustment completed)
C0 to C41 
setting 
is enabled.
Terminal 1 input
Terminal 4 input
Terminal 1 input Terminal 4 input
The parameter 
number read 
previously appears.
2. 
Press        to choose the parameter 
setting mode.
3. 
Turn         until              appears.
4. 
Press        to display             .
5. 
Turn        until              (             ) 
appears. Set to  C19 Terminal 1 gain (torque)
6. 
Press        to display the analog voltage 
(current) value (%).
7. 
Turn        to set the gain voltage (%). 
"0V (0mA) equals to 0%, 10V (5V, 
20mA) to 100%"
8. 
Press        to set.
REMARKS
The present setting at the instant of turning        
is displayed. 
By turning        , you can read another parameter.
Press        to return to the              display (step 4).
Press        twice to show the next parameter (            ).