Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
315
Selection of operation mode and operation location
4
(3) Operation mode selection flow
In the following flowchart, select the basic parameter setting and terminal connection related to the operation mode.
START
Connection
Parameter setting
Operation
Where is the start command 
source?
From external 
(STF/STR terminal)
Where is the frequency set?
From external 
(Terminal 2, 4, 
JOG, multi-speed, etc.)
STF (forward rotation)/STR 
(reverse rotation)
(Refer to page 231.)
Terminal 2, 4 (analog), RL, RM, 
RH, JOG, etc.
Frequency setting terminal ON
STF(STR) ON
From PU 
(Digital setting)
STF (forward rotation)/STR 
(reverse rotation)
(Refer to page 231.)
Pr.  79 = "3"
(External/PU combined 
operation 1)
DU digital setting
STF(STR) ON
From communication 
(RS-485 terminals/communication option)
RS-485 terminals or  
communication option?
RS-485 terminals
STF (forward rotation)/STR 
(reverse rotation)
(Refer to page 231.)
Connection of RS-485 terminals
(Refer to page 330.)
Pr. 338 = "1"
Pr. 340 = "1, 2"
Communication frequency setting 
command sending
STF(STR) ON
Communication option
Connection of communication 
option
(Refer to the corresponding communication 
option instruction manual)
Pr. 338 = "1"
Pr. 340 = "1"
Communication frequency setting 
command sending
STF(STR) ON
From PU 
(FWD/REV key)
Where is the frequency set?
From external 
(Terminal 2, 4, JOG, 
multi-speed, etc.)
Terminal 2, 4 (analog), RL, RM, 
RH, JOG, etc.
Pr. 79 = "4"
(External/PU combined 
operation 2)
Frequency setting terminal ON
FWD/REV key ON
From PU 
(Digital setting)
Pr. 79 = "1"
(Fixed to PU operation)
Digital setting
FWD/REV key ON
From communication 
(RS-485 terminals/communication option)
From communication 
(RS-485 terminals/communication option)
RS-485 terminals or  
communication option?
RS-485 terminals
Where is the frequency set?
From external
 (Terminal 2, 4, JOG, multi-speed, etc.)
Connection of RS-485 terminals
(Refer to page 330.)
Terminal 2, 4 (analog), RL, RM, 
RH, JOG, etc.
Pr. 339 = "1"
Pr. 340 = "1, 2"
Frequency setting terminal ON
Communication start command 
sending
From PU 
(Digital setting)
From communication
RS-485 terminals
Connection of RS-485 terminals
(Refer to page 330.)
Pr. 340 = "1, 2"
Communication frequency setting 
command sending
Communication start command 
sending
Communication option
Where is the frequency set?
From external 
(Terminal 2, 4, JOG, multi-speed, etc.)
Connection of communication option
(Refer to the corresponding communication 
option instruction manual)
Terminal 2, 4 (analog), RL, RM, 
RH, JOG, etc.
Pr. 339 = "1"
Pr. 340 = "1"
Frequency setting terminal ON
Communication start command 
sending
From PU 
(Digital setting)
From communication (
communication option)
Connection of communication option
(Refer to the corresponding communication 
option instruction manual)
Pr. 340 = "1"
Communication frequency setting 
command sending
Communication start command 
sending
Disabled
Disabled
Disabled