Special operation and frequency control
4
4.25 Special operation and frequency control
4.25.1 PID control (Pr. 127 to Pr. 134, Pr. 575 to Pr. 577)
Purpose
Parameter that must be Set
Refer 
to Page
Perform process control such as pump and air 
volume.
PID control
Pr. 127 to Pr. 134, 
Pr. 575 to Pr. 577
Switch between the inverter operation and 
bypass operation to operate.
Bypass-inverter switchover 
function
Pr. 135 to Pr. 139, Pr. 159
Increase speed when the load is light.
Load torque high speed 
frequency control
Pr. 4, Pr. 5, Pr. 270 to Pr. 274
Frequency control appropriate for the load torque
Droop control
Pr. 286 to Pr. 288
Frequency setting by pulse train input
Pulse train input
Pr. 291, Pr. 384 to Pr. 386
Make the motor speed constant by encoder
Encoder feedback control
Pr. 144, Pr. 285, Pr. 359, 
Pr. 367 to Pr. 369
Avoid overvoltage alarm due to regeneration by 
automatic adjustment of output frequency
Regeneration avoidance 
function
Pr. 882 to Pr. 886
The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure.
The terminal 2 input signal or parameter setting is used as a set point and the terminal 4 input signal used as a
feedback value to constitute a feedback system for PID control.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
127
PID control automatic 
switchover frequency
9999
 0 to 400Hz
Set the frequency at which the control is automatically 
changed to PID control.
9999
Without PID automatic switchover function
128
PID action selection
10
10
PID reverse action
Deviation value signal input
(terminal 1 )
11
PID forward action
20
PID reverse action
Measured value (terminal 4 ) 
Set point (terminal 2 or Pr. 133)
21
PID forward action
50
PID reverse action
Deviation value signal input
(L
ON
W
ORKS 
, CC-Link communication)
51
PID forward action
60
PID reverse action
Measured value, set point input
(L
ON
W
ORKS 
, CC-Link communication)
61
PID forward action
129 
*1
PID proportional band
100%
0.1 to 1000%
If the proportional band is narrow (parameter setting is small),
the manipulated variable varies greatly with a slight change of
the measured value. Hence, as the proportional band narrows,
the response sensitivity (gain) improves but the stability
deteriorates, e.g. hunting occurs. 
Gain Kp = 1/proportional band
9999
No proportional control
130 
*1
PID integral time
1s
0.1 to 3600s
When deviation step is input, time (Ti) is the time required for 
integral (I) action to provide the same manipulated variable as 
proportional (P) action.
As the integral time decreases, the set point is reached earlier 
but hunting occurs more easily.
9999
No integral control
131
PID upper limit
9999
 0 to 100%
Set the maximum value. If the feedback value exceeds the 
setting, the FUP signal is output. The maximum input (20mA/
5V/10V) of the measured value (terminal 4) is equivalent to 
100%.
9999
No function
132
PID lower limit
9999
 0 to 100%
Set the minimum value. If the measured value falls below the 
setting range, the FDN signal is output. The maximum input 
(20mA/5V/10V) of the measured value (terminal 4) is 
equivalent to 100%.
9999
No function
133 
PID action set point
9999
 0 to 100%
Used to set the set point for PID control.
9999
Terminal 2 input is the set point.