Inspection item
6.1.4
Display of the life of the inverter parts
The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan, each parts of the
inrush current limit circuit is near its end. It gives an indication of replacement time .
The life alarm output can be used as a guideline for life judgement.
 Refer to page 386 to perform the life check of the inverter parts.
6.1.5
Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
(2) Prepare a tester. (Use 100
Ω range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, P/+ and N/
−, and check
for conduction.
<Module device numbers and terminals to be checked>
(Assumes the use of an analog meter.)
6.1.6
Cleaning
Always run the inverter in a clean status.
When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol.
Parts
Judgement Level
Main circuit capacitor
85% of the initial capacity
Control circuit capacitor
Estimated 10% life remaining
Inrush current limit circuit
Estimated 10% life remaining (Power on: 100,000 times left)
Cooling fan
Less than 50% of the predetermined speed
CAUTION
1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of electric discontinuity, due to the smoothing capacitor, the tester may not indicate 
∞. At the time of electric
continuity, the measured value is several to several ten's-of ohms depending on the module type, circuit tester type, etc. If all
measured values are almost the same, the modules are without fault.
Tester Polarity
Measured 
Value
Tester Polarity
Measured 
Value
C
onv
er
ter
 
module
D1
R/L1
P/
+
Discontinuity
D4
R/L1
N/
Continuity
P/
+
R/L1
Continuity
N/
R/L1
Discontinuity
D2
S/L2
P/
+
Discontinuity
D5
S/L2
N/
Continuity
P/
+
S/L2
Continuity
N/
S/L2
Discontinuity
D3
T/L3
P/
+
Discontinuity
D6
T/L3
N/
Continuity
P/
+
T/L3
Continuity
N/
T/L3
Discontinuity
In
ve
rte
module
TR1
U
P/
+
Discontinuity
TR4
U
N/
Continuity
P/
+
U
Continuity
N/
U
Discontinuity
TR3
V
P/
+
Discontinuity
TR6
V
N/
Continuity
P/
+
V
Continuity
N/
V
Discontinuity
TR5
W
P/
+
Discontinuity
TR2
W
N/
Continuity
P/
+
W
Continuity
N/
W
Discontinuity
CAUTION
Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter surface paint to peel off.
The display, etc. of the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07) are vulnerable to detergent and
alcohol. Therefore, avoid using them for cleaning.
Converter module
Inverter module
D1
D2
D3
D4
D5
D6
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R/L1
S/L2
T/L3
C
P/+
N/