(5) Main differences and compatibilities with the FR-A500(L) series
Appendix 1-2 Replacement of the FR-A200 <EXCELENT> series
Instructions for installation
• When using the mounting holes of the FR-A200(E) series, FR-A5AT (intercompatibility attachment) is necessary.
Item
FR-A500(L)
FR-A700
Added 
functions
Control 
method
V/F control
Advanced magnetic flux vector control
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control 
(used with a plug-in option FR-A7AP/FR-A7AL)
PID control
PID action set point setting
(Pr. 133)
Addition of "9999" to PID action set point (Pr. 133
setting 
(a value input from terminal 2 is a set point)
Changed 
functions
Intelligent 
mode 
selection
Pr. 60
Parameter number change
(Pr. 60 Energy saving control selection)
(Pr. 292 Automatic acceleration/deceleration)
Motor poles
Number of motor poles
(Pr. 81 , Pr. 144)
Setting the number of motor poles in Number of motor 
poles (Pr. 81) automatically changes the speed setting 
switchover (Pr. 144) setting.
User group
User group 1 (16 parameters), User group 2 (16 
parameters) (Pr.160Pr.173 to Pr.175)
User group (16 parameters) only
Setting methods were partially changed
(Pr.160Pr.172 to Pr.173)
Communication 
option
Performing the parameter clear or all parameter 
clear (H5A96 or HAA99) from the DeviceNet 
communication option (FR-A5ND) clears the Pr. 
345
 and Pr. 346 settings.
Performing the parameter clear or all parameter clear 
(H5A96 or HAA99) from the DeviceNet communication 
option (FR-A7ND) does not clear the Pr. 345 and Pr. 346 
settings.
Deleted 
functions
User initial 
value setting 
(Pr. 199)
Available
Not available
Substitutable with the copy function of the operation 
panel (FR-DU07)
Long wiring 
mode
Pr. 240 setting 10, 11
Setting is not necessary
(Pr. 240 settings "10" and "11" were cleared) 
Program 
operation
Pr. 200 to Pr. 231
Function was cleared
Terminal block
Removable terminal block
Removable terminal block
Upward compatibility (FR-A500 terminal block 
mountable)
PU
FR-PU04, DU04
FR-PU07
FR-DU07
FR-PU04 (Some functions, such as parameter copy, 
are unavailable.)
FR-DU04 unavailable
Plug-in options
Dedicated plug-in option (incompatible)
Computer link, relay output option
FR-A5NR
Built into the inverter
(RS-485 terminals, relay output 2 points)
Installation size
· FR-A720-0.4K to 90K, FR-A740-0.4K to 7.5K, 18.5K to 55K, 110K, 160K are compatible in mounting 
dimensions.
For the FR-A740-11K, 15K, an optional intercompatibility attachment (FR-AAT) is necessary.
· Heatsink protrusion attachment is not compatible.
Also, the panel cut dimension of 3.7K or lower, 200V class 30K, 55K or higher, 400V class 11K, 15K, 75K 
or higher is not compatible.