Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
22/24
BCN-C22005-634
(2) List of automatically-set parameters
The following tables show which parameters are changed in each of the automatic parameter settings.
 GOT initial setting (PU connector) (Pr.999 = "10")
 GOT initial setting (RS-485 terminals) (Pr.999 = "11")
CAUTION
 If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the listed settings including
the changed parameter settings (changed from the initial setting) will be automatically changed. Before performing
the automatic setting, confirm that changing the listed parameters will not cause any problem. 
Parameter
Name
Initial 
value
Automatically set to
Refer to
79
Operation mode selection
0
1
Chapter 4 of the 
Instruction Manual 
(Applied)
118
PU communication speed
192
192
119
PU communication stop bit length
1
10
120
PU communication parity check
2
1
121
Number of PU communication 
retries
1
9999
122
PU communication check time 
interval
9999
9999
123
PU communication waiting time 
setting
9999
0ms
124
PU communication CR/LF selection
1
1
340
Communication startup mode 
selection
0
0
REMARKS
Always perform an inverter reset after the initial setting. 
Parameter
Name
Initial 
value
Automatically set to
Refer to
79
Operation mode selection
0
0
Chapter 4 of the 
Instruction Manual 
(Applied)
332
RS-485 communication speed
96
192
333
RS-485 communication stop bit 
length
1
10
334
RS-485 communication parity check 
selection
2
1
335
RS-485 communication retry count
1
9999
336
RS-485 communication check time 
interval
0s
9999
337
RS-485 communication waiting time 
setting
9999
0ms
340
Communication startup mode 
selection
0
1
341
RS-485 communication CR/LF 
selection
1
1
549
Protocol selection
0
0
REMARKS
Always perform an inverter reset after the initial setting. 
bcnc22005634.fm  22 ページ  2012年7月3日 火曜日 午前9時43分