71
Param
e
te
r List
Parameter List
4
4.2 Parameter List
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial value of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07). 
REMARKS
 
 indicates simple mode parameters. (initially set to extended mode)
The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write
selection
.
Refer to Appendix 2 (page 466) for instruction codes for communication and availability of parameter clear, all clear, and parameter copy of
each parameter.
Parameters with 
 have different specifications according to the date assembled. Refer to page 
 to check the SERIAL number.
Func-
tion
Parameter
Name
Setting Range
Minimum 
Setting
Increments
Initial Value
Refer 
to 
Page
Customer 
Setting
Ba
si
c f
unc
tions
 0
Torque boost
0 to 30%
0.1%
6/4/3/2
/1% 
*1
 1
Maximum frequency
0 to 120Hz
0.01Hz
120
/60Hz
 
 
*2
 2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
 3
Base frequency
0 to 400Hz
0.01Hz
60Hz
 4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
 5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
 6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
 7
Acceleration time
0 to 3600/360s
0.1/0.01s
5/15s 
*3
 
 8
Deceleration time
0 to 3600/360s
0.1/0.01s
5/15s 
*3
 9
Electronic thermal O/L relay
0 to 500/0 to 3600A 
*2
0.01
/0.1A 
*2
Rated inverter 
current
D
C inj
e
ct
io
n
 brak
e
10
DC injection brake operation frequency 0 to 120Hz, 9999
0.01Hz
3Hz
11
DC injection brake operation time
0 to 10s, 8888
0.1s
0.5s
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2
/1%
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
14
Load pattern selection
0 to 5
1
0
Jog 
op
erat
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
17
MRS input selection
0, 2, 4
1
0
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120
/60Hz 
*2
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
A
cce
le
ra
tio
n
/
de
ce
le
ra
tio
n
 ti
m
e
s
20
Acceleration/deceleration reference 
frequency
1 to 400Hz
0.01Hz
60Hz
21
Acceleration/deceleration time 
increments
0, 1
1
0
St
a
ll 
pr
ev
ent
ion
22
Stall prevention operation level
(torque limit level )
0 to 400%
0.1%
150%
23
Stall prevention operation level 
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
Mu
lti
-s
peed
se
tt
in
g
24 to 27
Multi-speed setting(4 speed to 7 speed)
0 to 400Hz, 9999
0.01Hz
9999
28
Multi-speed input compensation selection
0, 1
1
0
29
Acceleration/deceleration pattern 
selection
0 to 5
1
0
30
Regenerative function selection
0, 1, 2, 10, 11, 20, 21
1
0
F
req
uen
cy
 
ju
mp
31
Frequency jump 1A
0 to 400Hz, 9999
0.01Hz
9999
32
Frequency jump 1B
0 to 400Hz, 9999
0.01Hz
9999
33
Frequency jump 2A
0 to 400Hz, 9999
0.01Hz
9999
34
Frequency jump 2B
0 to 400Hz, 9999
0.01Hz
9999
35
Frequency jump 3A
0 to 400Hz, 9999
0.01Hz
9999
36
Frequency jump 3B
0 to 400Hz, 9999
0.01Hz
9999
37
Speed display
0, 1 to 9998
1
0