Справочник Пользователя для Hitachi L200

Скачать
Страница из 280
Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–10
The two diagrams below show input wiring circuits using the inverter’s internal +24V 
supply. Each diagram shows the connection for simple switches, or for a field device 
with transistor outputs. Note that in the lower diagram, it is necessary to connect 
terminal [L] only when using the field device with transistors. Be sure to use the correct 
SR/SK switch position shown for each wiring diagram.
L200
L
24V

SK
SR
SK
SR
PCS
Input 
circuits
1
5
Logic GND
1
5
GND
Open collector outputs, 
NPN transistors
Input 
switches
Sinking Inputs, Internal Supply
SR/SK switch = SK position
Field device
L200
L
24V

SK
SR
SK
SR
PCS
Input 
circuits
1
5
Common,
to [PCS]
1
5
GND
PNP transistor
sourcing outputs
Input 
switches
Sourcing Inputs, Internal Supply
SR/SK switch = SR position
Field device
to PNP bias  
circuits
Logic GND