4.2.34 Parameter write disable selection (Pr. 77)
Pr. 77 "parameter write disable selection"
You can select between write-enable and disable for parameters. This function is used to prevent parameter
values from being rewritten by accident.
<Setting>
Parameter 
Number
Factory
Setting
Setting Range
77
0
0, 1, 2
Pr. 77 Setting
Function
0
Write enabled during a stop only.
Parameter values may only be written during a stop in the PU operation mode. (Note 1)
1
Write disabled.
Values of Pr. 22, Pr. 75, Pr. 77 and Pr. 79 "operation mode selection" can be written.
2
Write enabled even during operation.
Note: 1. The values of the shaded parameters in the parameter list can be set at any time. (Refer to page
.
)
(Pr. 72 and Pr. 240 values cannot be set during external operation.)
2. If Pr. 77 = "2", the values of the following parameters cannot be written during operation. Stop
operation when changing their parameter settings.
Parameter 
Number
Name
Parameter 
Number
Name
23
Stall prevention operation level 
compensation factor at double speed
107
V/F4 (fourth frequency voltage)
48
Second stall prevention operation 
current
108
V/F5 (fifth frequency)
49
Second stall prevention operation 
frequency
109
V/F5 (fifth frequency voltage)
60
Intelligent mode selection
135
Commercial power supply-inverter 
switch-over sequence output 
terminal selection
61
Reference current
136
MC switch-over interlock time
66
Stall prevention operation reduction 
starting frequency
137
Start waiting time
71
Applied motor
138
Commercial power supply-inverter 
switch-over selection at alarm 
occurrenc
79
Operation mode selection
139
Automatic inverter-commercial 
power supply switch-over frequency
80
Motor capacity
180
RL terminal function selection
81
Number of motor poles
181
RM terminal function selection
83
Rated motor voltage
182
RH terminal function selection
84
Rated motor frequency
183
RT terminal function selection
95
Advanced mode selection
184
AU terminal function selection
96
Auto tuning setting/status
185
JOG terminal function selection
100
V/F1 (first frequency)
186
CS terminal function selection
101
V/F1 (first frequency voltage)
190
RUN terminal function selection
102
V/F2 (second frequency)
191
SU terminal function selection
103
V/F2 (second frequency voltage)
192
IPF terminal function selection
104
V/F3 (third frequency)
193
OL terminal function selection
105
V/F3 (third frequency voltage)
194
FU terminal function selection
106
V/F4 (fourth frequency)
195
A, B, C terminal function selection
3. By setting "1" in Pr. 77, the following clear operations can be inhibited:
•Parameter clear
•All clear
•User clear
Pr. 79 "operation mode selection"
Related parameters