4.2.37 Motor capacity/number of motor poles/speed control gain (Pr. 80, 
Pr. 81, Pr. 89)
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 89 "speed control gain"
You can set the advanced magnetic flux vector control.
z
 Advanced magnetic flux vector control
Provides large starting torque and sufficient low-speed torque.
Effective for great load fluctuation.
If any of the following conditions is not satisfied, faults such as torque shortage and speed fluctuation may
occur. In this case, select V/F control.
<Operating conditions>
• The motor capacity is equal to or one rank lower than the inverter capacity.
• The motor type is the Mitsubishi standard motor (SF-JR 2-poles, 4-poles, 6-poles, 0.4kW or more) or
Mitsubishi constant-torque motor (SF-JRCA 200V class 4-poles motor of 0.4kW to 55kW. Always perform
offline auto tuning for any other motor (e.g. other manufacturer’s motor, SF-JRC).
• Single-motor operation (one motor for one inverter) is performed.
• The wiring length between the inverter and motor is within 30m. (If the length is over 30m, perform offline
auto tuning with the cables wired.)
<Setting>
(1)
 
Advanced magnetic flux vector control
•By setting the capacity, number of poles and type of the motor used in Pr. 80 and Pr. 81, the advanced
magnetic flux vector control can be selected.
• When using the Mitsubishi constant-torque motor (SF-JRCA), set "1" in Pr. 71. (When using the SF-JRC,
perform the offline auto tuning .)
• When using the Mitsubishi standard motor (SF-JR, 4P, 1.5kW or less), set "20" in Pr. 71.
Parameter 
Number
Factory
Setting
Setting Range
Remarks
80
9999
0.4K to 55kW, 9999
9999: V/F control
81
9999
2, 4, 6, 12, 14, 16, 9999
9999: V/F control
89
100%
0 to 200.0%
Parameter
Number
Setting
Description
80
9999
V/F control
0.4 to 55
Set the motor capacity applied.
Advanced magnetic flux vector control
81
9999
V/F control
2, 4, 6
Set the number of motor poles.
Advanced magnetic flux vector control
12, 14, 16
V/F control is selected when the X18 (magnetic flux-
V/F switch-over) signal switches on.
(This selection is not made during operation.)
Use any of Pr. 180 to Pr. 186 to assign the terminal 
used for X18 signal input.
12: For 2-pole motor
14: For 4-pole motor
16: For 6-pole motor
Related parameters
Pr. 71 "applied motor"
Pr. 83 "rated motor voltage"
Pr. 84 "rated motor frequency"
Pr. 89 "speed control gain"
Pr. 90 to Pr. 94 (motor constants)
Pr. 95 "online auto tuning selection"
Pr. 96 "auto tuning setting/status"
Pr. 180 to Pr. 186
(input terminal function selection)